Service Manual 133
Operation Details
■
Chaos Swing Mode
• By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they
are fixed to the desired direction.
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
■
Chaos Natural Wind Mode
• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the
airflow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
■
Jet Cool Mode Operation
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
■
Forced Operation
• Operation procedures when the remote control can't be used.
• The operation will be started if the power button is pressed.
• If you want to stop operation, re-press the button.
• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times
to indicate the forced operation.
Room temperature
≥
24°C
21°C
≤
Room temperature < 24°C
Room temperature < 21°C
Operating mode
Cooling
Healthy Dehumidification
Heating
Indoor FAN Speed
High
High
High
Setting Temperature
22°C
23°C
24°C
CLOSED
OPEN
< Cooling Mode >
7
°
CLOSED
OPEN
< Heating Mode >
7
°
Summary of Contents for multi V PLUS
Page 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Page 74: ...74 Indoor Unit ...
Page 86: ...86 Indoor Unit ...
Page 142: ...142 Indoor Unit ...
Page 160: ...160 Indoor Unit ...
Page 179: ...Service Manual 179 Outdoor unit ...
Page 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Page 245: ...Service Manual 245 Trouble shooting guide ...
Page 296: ...296 Trouble Shooting Guide ...
Page 297: ...Service Manual 297 Appendix ...
Page 303: ...Service Manual 303 Exploded View Replacement Parts List ...