Service Manual 213
Function
3.1 Pressure protection control
3.1.1 Pressure control on cooling mode
■
High pressure control
■
Low pressure control(above -10˚C)
• Hot gas bypass off condition : if hot gas bypass valve is on, the valve turn off above 399 kPa
3. Protection control
2284kPa <Pc ≤ 2422kPa
No frequency up
5 Hz down/sec
High pressure
control
10 Hz up/sec
System stop
2441kPa <Pc ≤ 2657 kPa
Pc>2657kPa
Pc ≤ 2284kPa
Low pressure
control
High pressure
control
Pressure range
Compressor
Fan
-
-
-
Hot gas
bypass
49 kPa< Pe ≤ 62kPa
5 Hz down/sec
Low pressure
control
5 Hz down/sec
No frequency up
System stop
62 kPa< Pe ≤ 101kPa
Pe >101kPa
Pe ≤ 49 kPa
Low pressure
control
High pressure
control
Pressure range
Compressor
Fan
On
On
-
Hot gas
bypass