150
Indoor Unit
Operation Details
■
Heating Mode Operation
• When the intake air temperature r3°C above the setting temperature, the compressor is turned
off. When below the setting temperature, the compressor is turned on.
Compressor ON temperature
➲
Setting temperature
Compressor OFF temperature
➲
Setting temp3°C
• While in compressor on, the indoor fan is off when the indoor pipe temperature is below 20°C, when above
28°C, it operates with the low or setting airflow speed. When the indoor pipe temperature is between 20°C
and 28°C, it operates with Super-Low(while in sleep mode, with the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temperature is below 33°C, when above
35°C , it operates with the low airflow speed.
• If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the
outdoor fan is turned on/off according to the indoor pipe temperature
• While in defrost control, both of the indoor and outdoor fans are turned off.
■
Fuzzy Operation
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed
since the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and
only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake
air temperature at that moment as follows.
24°C
≤
Inatake Air Temperature
➲
Fuzzy Operation for Cooling
21°C
≤
Inatake Air Temperature <24°C
➲
Fuzzy Operation for Dehumidification
Inatake Air Temperature <21°C
➲
Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for
10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
• According to the setting temperature selected by Fuzzy rule, when the intake air temperature is 0.5°C or
more below the setting temperature, the compressor is turned off. When 0.5°C or more above the setting
temperature, the compressor is turned on.
Compressor ON Temperature
➲
Setting Temperature +0.5°C
Compressor OFF Temperature
➲
Setting Temperature + 0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to
the intake air temperature at that time.
26°C
≤
Intake Air Temperature
➲
25°C
24°C
≤
Intake Air Temperature <26°C
➲
Intake Air Temperature + 1°C
22°C
≤
Intake Air Temperature <24°C
➲
Intake Air Temperature + 0.5°C
18°C
≤
Intake Air Temperature <22°C
➲
Intake Air Temperature
Intake Air Temperature <18°C
➲
18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the tem-
perature.
Summary of Contents for multi V PLUS
Page 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Page 74: ...74 Indoor Unit ...
Page 86: ...86 Indoor Unit ...
Page 142: ...142 Indoor Unit ...
Page 160: ...160 Indoor Unit ...
Page 179: ...Service Manual 179 Outdoor unit ...
Page 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Page 245: ...Service Manual 245 Trouble shooting guide ...
Page 296: ...296 Trouble Shooting Guide ...
Page 297: ...Service Manual 297 Appendix ...
Page 303: ...Service Manual 303 Exploded View Replacement Parts List ...