Service Manual 97
Operation Details
INDOOR FAN
Low Fan
Low Fan
Intake Air temperature
Setting tempe1.0˚C
(Compressor ON)
Setting temperature -0.5˚C
(Compressor OFF)
Setting temperature
2min.58sec.
2min.58sec.
10min.
10min.
7min.
Within 7min. Cooling
Cooling
OUTDOOR FAN
COMPRESSOR
Selected
Fan
Selected
Fan
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
■
Soft Dry Operation
• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, the compressor
OFF temperature is the setting temperature minus 0.5°C.
• When the room temperature rises over the compressor ON temperature, the operation mode is switched to
the cooling mode.
• When the room temperature falls between the compressor ON temperature and OFF temperature, the opera-
tion mode is switched to the Soft Dry Operation.
In this temperature range, 10min. Dry Operation, 7min operation OFF. During 10min Dry operation, if the room
temperature falls below compressor OFF temperature, Compressor OFF.
• In dehumidify mode, control of fan speed is as following.
■
Forced operation
• If you lose wireless remote controller, you can operate the unit with forced operation switch.
• The standard conditions are as following.
• Unit operates in low fan mode for first 15 seconds, then switched to proper operation mode according to
intake Air temperature.
Room Temperature
24°C
21°C Room Temperature 24°C
Room Temperature 21°C
Operation Mode
Cooling
Soft Dry
Heating
FAN Speed
High
Soft Dry Rule
High
Setting Temperature
22°C
Air Intake Temperature
24°C
R
Forced
Operation Button
Press the Forced Operation Button.
• Press the Forced Operation Button once
again to stop operation.
Summary of Contents for multi V PLUS
Page 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Page 74: ...74 Indoor Unit ...
Page 86: ...86 Indoor Unit ...
Page 142: ...142 Indoor Unit ...
Page 160: ...160 Indoor Unit ...
Page 179: ...Service Manual 179 Outdoor unit ...
Page 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Page 245: ...Service Manual 245 Trouble shooting guide ...
Page 296: ...296 Trouble Shooting Guide ...
Page 297: ...Service Manual 297 Appendix ...
Page 303: ...Service Manual 303 Exploded View Replacement Parts List ...