Service Manual 215
Function
3.2 Discharge temperature control
■
Outdoor unit's control on cooling, heating mode
■
Indoor unit's control on cooling, heating mode
Emergency
SH control
System stop
103< Tdis
≤
115 ˚C
Tdis >115 ˚C
Temperature range
LEV
Keep current control
98 ˚C < Tdis
≤
103 ˚C
SH control
Tdis
≤
98 ˚C
If liquid injection is on,
No frequency up,
After 2min
→
5Hz/30sec
System stop
103< Tdis
≤
115 ˚C
Tdis >115 ˚C
Temperature range
Compressor
On
Liquid
injection
If liquid injection is on,
No frequency up,
After 2min
→
5Hz/30sec
98 ˚C < Tdis
≤
103 ˚C
Keep
state
Pressure control
Tdis
≤
98 ˚C
Off
Max. limit
300 pulse
Subcooling
LEV
If liquid is on,
Max. limit
300 pulse
Max. limit
150 pulse
Pressure control
Tdis >95 ˚C
Off
10 pulse open
/10sec