Service Manual 153
Operation Details
■
Forced Operation
• Operation procedures when the remote control can't be used.
• The operation will be started if the power button is pressed.
• If you want to stop operation, re-press the button.
• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times
to indicate the forced operation.
■
Test operation
•
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room
temperature and resets in 18±1 minutes.
•
During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, open the front panel upward and Press the power button let it be pressed
for about 3 seconds.
•
If you want to stop the operation, re-press the button.
■
Auto restart
•
In case the power comes on again after a power failure, Auto Restarting Operation is the function to oper-
ate procedures automatically to the previous operating conditions.
■
Remote Control Operation Mode
• When the remote control is selected by the slide switch on the main unit, the appliance operates according
to the input by the remote control.
■
Protection of the evaporator pipe from frosting
• If the indoor pipe temperature is below 0°C in 7 min. after the compressor operates without any pause while
in cooling cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the
indoor evaporator pipe from frosting.
• When the indoor pipe temperature is 7°C or higher after 3 min. pause of the compressor, the compressor
and the outdoor fan is turned on according to the condition of the room temperature.
■
Buzzer Sounding Operation
• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
• When the appliance-pause key is input by the remote control, the long "beep—" sounds.
• When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that
the remote control signal cannot be received.
Room temperature
≥
24°C
21°C
≤
Room temperature < 24°C
Room temperature < 21°C
Operating mode
Cooling
Healthy Dehumidification
Heating
Indoor FAN Speed
High
High
High
Setting Temperature
22°C
23°C
24°C
Summary of Contents for multi V PLUS
Page 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Page 74: ...74 Indoor Unit ...
Page 86: ...86 Indoor Unit ...
Page 142: ...142 Indoor Unit ...
Page 160: ...160 Indoor Unit ...
Page 179: ...Service Manual 179 Outdoor unit ...
Page 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Page 245: ...Service Manual 245 Trouble shooting guide ...
Page 296: ...296 Trouble Shooting Guide ...
Page 297: ...Service Manual 297 Appendix ...
Page 303: ...Service Manual 303 Exploded View Replacement Parts List ...