Service Manual 47
Operation detail
3. Operation detail
■
Time Delay Safety Control
• 5 sec... Vertical air flow direction control louvers open in 5 seconds to prevent noise between louvers and wind.
• 5 sec... The 4-way valve is ceased for 5 sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode when compress is off.
While compressor is running, it takes 3~5 seconds to switch.
■
Auto Swing Control
• This function is to swing the louver up and down automatically.
■
Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
■
Cooling Mode Operation
• When selecting the Cooling(
) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
Intake Air Temperature
COMP. ON
(SET TEMPE0.5°C)
COMP. OFF
(SET TEMPERATURE -0.5°C)
More than
More than
3 minutes
3 minutes
Selecting
Selecting
Selecting
fan speed
fan speed
fan speed
INDOOR FAN
Low Low
(1) The function of main control
Summary of Contents for multi V PLUS
Page 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Page 74: ...74 Indoor Unit ...
Page 86: ...86 Indoor Unit ...
Page 142: ...142 Indoor Unit ...
Page 160: ...160 Indoor Unit ...
Page 179: ...Service Manual 179 Outdoor unit ...
Page 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Page 245: ...Service Manual 245 Trouble shooting guide ...
Page 296: ...296 Trouble Shooting Guide ...
Page 297: ...Service Manual 297 Appendix ...
Page 303: ...Service Manual 303 Exploded View Replacement Parts List ...