Trouble Shooting Guide
Self-diagnosis function
Fault diagnosis and Trouble shooting guide
35
144
146
Error Item
Error
Display No.
Major Error Occurrence Cause
Meaning
35: Low pressure drop of
main outdoor unit
144: Low pressure drop
of Sub1 outdoor unit
144: Low pressure drop
of Sub2 outdoor unit
Compressor stops by
excessive drop of low
pressure
• Failure of low pressure sensor or low
pressure sensor detection circuit part
• Clogging of service valve
• Insufficient refrigerant
• Leakage of refrigerant
• Poor indoor pipe temperature sensor
• Failure of indoor/outdoor unit fan
• Check communication lines of indoor units.
• Check LEV connection of indoor unit PCB.
Trouble shooting Flow
No
No
Replace the PCB.
Yes
Yes
Replace the low
pressure sensor.
Is suction pressure (low pressure)
actually high?
Is the pressure sensor normal?
No
Check the outdoor/indoor LEV.
Yes
Modify wiring.
Check or replace the fan.
Is the LEV of the indoor/outdoor
unit normal?
Are communication lines normal?
No
No
Yes
Yes
Is the fan of the indoor/outdoor
unit normal?
Check open status of the service valve.
Check clogging of pipe or status of refrigerant.
Summary of Contents for multi V PLUS
Page 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Page 74: ...74 Indoor Unit ...
Page 86: ...86 Indoor Unit ...
Page 142: ...142 Indoor Unit ...
Page 160: ...160 Indoor Unit ...
Page 179: ...Service Manual 179 Outdoor unit ...
Page 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Page 245: ...Service Manual 245 Trouble shooting guide ...
Page 296: ...296 Trouble Shooting Guide ...
Page 297: ...Service Manual 297 Appendix ...
Page 303: ...Service Manual 303 Exploded View Replacement Parts List ...