90
COMMISSIONING MANUAL
POWERDRIVE MD
Variable speed drive
MENUS AND DIAGRAMS IN ADVANCED SET UP MODE
LEROY-SOMER
3871 en - 2011.05 / h
: Binary sum output offset
Adjustment range : 0 to 32
Factory setting
: 0
Used to add an offset to the binary sum output.
to
: Not used
to
: Binary sum 2
sources
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
Used to modify, using a combination of binary parameters, a
parameter whose selection includes more than 2 possible
choices.
09.52
:
Source bit 0
09.53
:
Source bit 1
09.54
:
Source bit 2
: Binary sum 2 output offset
Adjustment range : 0 to 32
Factory setting
: 0
Used to add an offset to the binary sum 2 output.
: Binary sum 2 output
Adjustment range : 0 to 39
Used to read the decimal value of binary sum 2 output.
: Binary sum 2 destination
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
Used to define the parameter that binary sum 2 output will
control.
Any bit, switch or numerical type parameter can be assigned
to the binary sum 2 output.
to
: Not used
: Lo
g
ic 3 output destination
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
This parameter defines the internal parameter which will be
assigned by the output of logic function 3.
Only non-protected "bit" type parameters can be addressed.
If an unsuitable parameter is programmed, the destination will
not be taken into account.
: Lo
g
ic function 3 out
Adjustment range : Disabled (0) or Enabled (1)
Indicates the state of the output of logic function 3.
and
: Not used
: Lo
g
ic function 3 source 1
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
This parameter is used to select source 1 for logic function 3.
Only "bit" type parameters can be used on these inputs.
If an unsuitable parameter is addressed, the input will be
frozen at 0.
: Lo
g
ic 3 source 1 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting
: Disabled (0)
This parameter is used to invert source 1 of logic function 3.
Disabled (0): Source 1 not inverted.
Enabled (1):
Source 1 inverted.
: Lo
g
ic function 3 source 2
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
This parameter is used to select source 2 for logic function 3.
Only "bit" type parameters can be used on these inputs.
If an unsuitable parameter is addressed, the input will be
frozen at 0.
: Lo
g
ic 3 source 2 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting
: Disabled (0)
This parameter is used to invert source 2 of logic function 3.
Disabled (0): Source 2 not inverted.
Enabled (1):
Source 2 inverted.
: Lo
g
ic 3 output invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting
: Disabled (0)
This parameter is used to invert the output of logic function 3.
Disabled (0): Output not inverted.
Enabled (1):
Output inverted.
: Not used
: Lo
g
ic 4 output destination
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
This parameter defines the internal parameter which will be
assigned by the output of logic function 4.
Only non-protected "bit" type parameters can be addressed.
If an unsuitable parameter is programmed, the destination will
not be taken into account.
: Lo
g
ic function 4 out
Adjustment range : Disabled (0) or Enabled (1)
Indicates the state of the output of logic function 4.
09.54
09.53
09.52
Decimal conversion
0
0
0
0
0
0
1
1
0
1
0
2
0
1
1
3
1
0
0
4
1
0
1
5
1
1
0
6
1
1
1
7
09.34
09.35
09.51
09.52
09.54
09.55
09.56
09.57
09.58
09.59
09.60
09.61
09.62
09.63
09.64
09.65
09.66
09.67
09.68
09.69
09.70
09.71