21
COMMISSIONING MANUAL
POWERDRIVE MD
Variable speed drive
PARAMETER SETTING INTERFACE
LEROY-SOMER
3871 en - 2011.05 / h
2.4.5 - Commissionin
g
usin
g
the user menu (menu 0)
2.4.5.1 - List of parameters
: V/F open loop flux vector control mode (see
00.13
).
: Servo or closed loop flux vector control mode (see
00.13
).
Ico : Continuous output current.
Parameter
Name
Address Mode
Adjustment ran
g
e
Factory settin
g
List of parameters
00.01
to
00.45
00.01
MINIMUM REFERENCE CLAMP
01.07
0 to
00.02
rpm
0 rpm
00.02
MAXIMUM REFERENCE CLAMP
01.06
0 to 32000 rpm
1500 rpm
00.03
ACCELERATION RATE 1
02.11
0.1 to 3200.0 s/1000 rpm, 100 rpm
20.0 s/1000 rpm
00.04
DECELERATION RATE 1
02.21
0.1 to 3200.0 s/1000 rpm, 100 rpm
20.0 s/1000 rpm
00.05
REFERENCE SELECTOR
01.14
Term. inputs, Analog 1, Analog 2,
Preset, Keypad
Term. inputs
00.06
MOTOR RATED CURRENT
05.07
0 to Ico (A)
(depends on the rating,
refer to section 5.6.3)
00.07
MOTOR RATED SPEED
05.08
1 to 32000 rpm
(depends on the rating,
refer to section 5.6.3)
00.08
MOTOR RATED VOLTAGE
05.09
0 to 999 V
400 V
00.09
RATED POWER FACTOR
05.10
0.00 to 1.00
0.85
00.10
MOTOR RATED FREQUENCY
05.06
0.0 to 999.9 Hz
50.0 Hz
00.11
NUMBER OF MOTOR POLES
05.11
Automatic, 2 Poles, 4 Poles,
6 Poles, 8 Poles, 10 Poles, 12 Poles,
14 Poles, 16 Poles
Automatic
00.12
MAXIMUM SWITCHING
FREQUENCY
05.18
1,5 - 2 - 2.5 - 3 - 3.5 - 4 - 4.5 - 5 - 5.5 - 6
3 kHz
6.5 - 7 - 8 - 9 - 10 - 11 - 12 - 13 - 14 kHz
00.13
USER DRIVE MODE
11.31
OPEN LOOP,
OPEN LOOP
CL LP Vector, SERVO,
REGEN,
Syn VS REGEN,
Asy VS REGEN, CONV DC/DC
00.14
OPEN LOOP MODE SELECT
05.14
RS: EACH RUN,
RS: NO Mes.,
RS: LINEAR V/F,
RS: 1st RUN,
RS: POWER UP,
RS: V/F SQUARE
RS: NO Mes.
ENCODER TYPE
03.38
INCREMENTAL,
Increm. FD,
U, V, W only,
Increm. UVW,
HALL EFFECT,
SENSORLESS 1 to 5, RESOLVER
INCREMENTAL
00.15
LOW FREQUENCY VOLTAGE
BOOST
05.15
0.0 to 25.0%
1.0%
ENCODER LINES PER
REVOLUTION
03.34
0 to 32000 lines/revolution
1024 lines/revolution