88
COMMISSIONING MANUAL
POWERDRIVE MD
Variable speed drive
MENUS AND DIAGRAMS IN ADVANCED SET UP MODE
LEROY-SOMER
3871 en - 2011.05 / h
5.10.2 - Explanation of parameters in menu 9
: Lo
g
ic function 1 out
: Lo
g
ic function 2 out
Adjustment range : Disabled (0) or Enabled (1)
Indicate the state of the output of logic functions 1 and 2.
: Motorised pot reference
Adjustment range : ± 100.0%
: Lo
g
ic function 1 source 1
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
This parameter is used to select source 1 for logic function 1.
Only "bit" type parameters can be used on this input.
If an unsuitable parameter is addressed, the input will be
frozen at 0.
: Lo
g
ic 1 source 1 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting
: Disabled (0)
This parameter is used to invert source 1 of logic function 1.
Disabled (0): Source 1 not inverted.
Enabled (1):
Source 1 inverted.
: Lo
g
ic function 1 source 2
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
This parameter is used to select source 2 for logic function 1.
Only "bit" type parameters can be used on this input.
If an unsuitable parameter is addressed, the input will be
frozen at 0.
: Lo
g
ic 1 source 2 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting
: Disabled (0)
This parameter is used to invert source 2 of logic function 1.
Disabled (0): Source 2 not inverted.
Enabled (1):
Source 2 inverted.
: Lo
g
ic 1 output invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting
: Disabled (0)
This parameter is used to invert the output of logic function 1.
Disabled (0): Output not inverted.
Enabled (1):
Output inverted.
: Not used
: Lo
g
ic 1 output destination
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
This parameter defines the internal parameter which will be
assigned by the output of logic function 1.
Only unprotected "bit" type parameters can be addressed.
If an unsuitable parameter is programmed, the destination will
not be taken into account.
to
: Not used
: Lo
g
ic function 2 source 1
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
This parameter is used to select source 1 for logic function 2.
Only "bit" type parameters can be used on this input.
If an unsuitable parameter is addressed, the input will be
frozen at 0.
: Lo
g
ic 2 source 1 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting
: Disabled (0)
This parameter is used to invert source 1 of logic function 2.
Disabled (0): Source 1 not inverted.
Enabled (1):
Source 1 inverted.
: Lo
g
ic function 2 source 2
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
This parameter is used to select source 2 for logic function 2.
Only "bit" type parameters can be used on these inputs.
If an unsuitable parameter is addressed, the input will be
frozen at 0.
: Lo
g
ic 2 source 2 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting
: Disabled (0)
This parameter is used to invert source 2 of logic function 2.
Disabled (0): Source 2 not inverted.
Enabled (1):
Source 2 inverted.
: Lo
g
ic 2 output invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting
: Disabled (0)
This parameter is used to invert the output of logic function 2.
Disabled (0): Output not inverted.
Enabled (1):
Output inverted.
: Not used
09.01
09.02
09.03
09.04
09.05
09.06
09.07
09.08
09.09
09.10
09.11
09.13
09.14
09.15
09.16
09.17
09.18
09.19