143
COMMISSIONING MANUAL
POWERDRIVE MD
Variable speed drive
TRIPS - DIAGNOSTICS
LEROY-SOMER
3871 en - 2011.05 / h
36
U sign. loss
• Loss of encoder commutation channel U
• Check the speed feedback
• Replace the encoder
37
V sign. loss
• Loss of encoder commutation channel V • Check the encoder voltage and connections
38
Breakdown
• Breakdown of synchronous motor in
sensorless closed loop mode
• Check the machine configuration in
05.17
,
05.24
,
05.33
and
05.51
41
User 1
• User 1 trip triggered by state 1 of
10.61
• In factory settings, overload of the
drive or the braking resistor
• See
10.17
to
10.19
.
• See
10.61
42
User 2
• User 2 trip triggered by state 1 of
10.63
• See
10.63
43
User 3
• User 3 trip triggered by state 1 of
10.65
• See
10.65
44
User 4
• User 4 trip triggered by state 1 of
10.67
• See
10.67
45
User 5
• User 5 trip triggered via serial link
• See
10.38
• See
10.37
46
User 6
• User 6 trip triggered via serial link
• See
10.38
• See
10.37
47
User 7
• User 7 trip triggered via serial link
• See
10.38
• See
10.37
48
User 8
• User 8 trip triggered via serial link
• See
10.38
• See
10.37
49
User 9
• User 9 trip triggered via serial link
• See
10.38
• See
10.37
50
User 10
• User 10 trip triggered via serial link
• See
10.38
• See
10.37
51
PXIO EEPROM • Problem on PX-I/O EEPROM
• Power down and then power up again
• Return to factory settings
(see
00.45
)
52
PXIO power
• Overload of the PX-I/O power supply
• Loss of 24 V detected by the option
• Check the current consumption
• Make sure there has not been a temporary overload of
the 24 V
53
PXIO CLOCK
• Problem on the real-time clock of the
PX-I/O
• Power down and then power up again
• Set the time again
54
PXIO COMM
• Communication problem between the
drive and the PX-I/O
• Power down the drive, then check that the option
is positioned correctly
56
IGBT V
• Trip on an IGBT (V)
• Reduce the motor load, the cycle, the switching frequency
(see
00.12
or
05.18
), and lengthen the acceleration
ramp (see
00.03
or
02.11
) and deceleration ramp
(see
00.04
or
02.21
).
57
IGBT W
• Trip on an IGBT (W)
• Reduce the motor load, the cycle, the switching frequency
(see
00.12
or
05.18
), and lengthen the acceleration
ramp (see
00.03
or
02.11
) and deceleration ramp
(see
00.04
or
02.21
).
58
Th IGBT V
• IGBT (V) overheating, ventilation
problem, ambient temperature too
high
• Load too great
• Check the ambient temperature
• Check the drive load level
• Check that all the fans are working
• Check the state of the door filters
• Check the frequency and temperature derating of the
drive (see Installation manual)
No.
Confi
g
uration
interface name
Reason for trip
Solution