![Lamtec BT300 BurnerTronic Manual Download Page 57](http://html1.mh-extra.com/html/lamtec/bt300-burnertronic/bt300-burnertronic_manual_3442242057.webp)
56
4
Design and Functions
p
1
V
1
= p
2
V
2
p = absolute pressure
V = gas volume
This is valid for the test of valve 1 V1:
Should t3 be negative, at least 1s must be set.
If the calculation of t3 for valve 2 is higher than t3 for valve 1, the value for the calculation of
valve 2 must be adjusted.
NOTICE
p
Schalt
must always be higher than p
out.
Otherwise V1 would be recognised as leaking even if it is not.
This is valid for the test of valve 2 V2:
If t3 is negative, at least 1 s must be set.
If the calculated t3 value of valve 1 is higher than t3 for valve 2, the calculated value of valve
1 must be adjusted.
Q
leak
Leakage rate in l/h
p
sw
Absolute pressure on the switching point of pressure monitor (adjusted over-
pr atmosphere pressure)
p
sw e
Adjusted overpressure on switching point of pressure monitor
p
out e
Output pressure on gas valve V2 during purge
p
Atm
Atmospheric pressure (average of 101,3 kPa at sea level)
V
test
Test volume between the valves
t2
Settling time is always 2 s
t3
Adjusted leakage check time
Q
leak
Leakage rate in l/h
p
sw
Absolute pressure on switching point of pressure monitor (adjusted overpres-
sure + atmosphere pressure)
p
sw e
Adjusted overpressure on the switching point of pressure monitor
p
in
Absolute input pressure on gas valve V1
p
in e
Overpressure at gas valve V1 input
p
Atm
Atmosphere pressure (average of 101,3 kPa at sea level)
V
test
Test volume between the valves
t2
Settling time is always 2 s
t3
Adjusted leakage check time
Summary of Contents for BT300 BurnerTronic
Page 2: ......
Page 25: ...24 3 Product Description Fig 3 9 Temperature derating BT300 for operation 2000 m NHN...
Page 49: ...48 4 Design and Functions Fig 4 20 Oil with pilot burner BT300...
Page 50: ...49 4 Design and Functions Fig 4 21 Oil without pilot burner BT300...
Page 51: ...50 4 Design and Functions Fig 4 22 Gas with pilot burner and leakage test BT300...
Page 52: ...51 4 Design and Functions Fig 4 23 Gas without pilot burner and leakage test BT300...
Page 53: ...52 4 Design and Functions Fig 4 24 Oil without pilot burner BT335...
Page 54: ...53 4 Design and Functions Fig 4 25 Gas without pilot burner and leakage test BT335...
Page 59: ...58 4 Design and Functions Fig 4 28 Leakage test process diagram...
Page 98: ...97 6 Operating Control and Displays...
Page 99: ...98 6 Operating Control and Displays...
Page 103: ...102 6 Operating Control and Displays...
Page 105: ...104 6 Operating Control and Displays...
Page 106: ...105 6 Operating Control and Displays...
Page 107: ...106 6 Operating Control and Displays...
Page 109: ...108 6 Operating Control and Displays...
Page 126: ...125 6 Operating Control and Displays 6 3 4 2 Curve Table Fig 6 37 Curve table window...
Page 246: ...242 10 EU Declaration of Conformity 10 EU Declaration of Conformity...
Page 247: ...243 10 EU Declaration of Conformity...