218
8
Options
8.5.2
Field Bus Module for MODBUS TCP EBM100
The burner control system communicates via LAMTEC SYSTEM BUS (LSB) with its modules
consistently. The MODBUS module EBM100 integrates LAMTEC burner control system into
fieldbus environment (MODBUS TCP). EBM100 listens for different, measured process val-
ues on LSB, processes these signals and transfers them to fieldbus.
NOTICE
The communication devices of other manufacturers connected to the communication interfac-
es (Ethernet) must demonstrably fulfil the safety-related requirements for classes ES1 and
PS1 according to DIN EN IEC 62368:2021-05.
8.5.2.1 IP Configuration
EBM100 network default configuration:
•
Dynamic IP address: DHCP
•
Subnet mask: 255.255.255.0 (fix, it cannot be changed)
The IP address is pre-set in BT300 parameters 765 and 766 (BT300 v3.3 and higher).
If EBM100 can’t read the parameters during start-up, the last configured IP address remains
active.
For your information the red LED is flushing in addition to the Ethernet LED.
Example: 192.168.2.100:
P 7665 = C0A8 (HEX) = 49320 (DEZ)
P 766 = 0264 (HEX) = 612 (DEZ)
If P 765 and P 766 are not configured (default = 0 for each), or both parameters are set to 0,
the IP configuration of EBM100 is set to DHCP.
Presetting of the IP address
P 765
MSByte
1. octet
P 765
LSByte
2. octet
P 766
MSByte
3. octet
P 766
LSByte
4. octet
Unit
1. Octet
2. Octet
3. Octet
4. Octet
DEZ
192
168
2
100
Parameter
MSByte P 765
LSByte P 765
MSByte P 766
LSByte P 766
HEX
C0
A8
02
64
Summary of Contents for BT300 BurnerTronic
Page 2: ......
Page 25: ...24 3 Product Description Fig 3 9 Temperature derating BT300 for operation 2000 m NHN...
Page 49: ...48 4 Design and Functions Fig 4 20 Oil with pilot burner BT300...
Page 50: ...49 4 Design and Functions Fig 4 21 Oil without pilot burner BT300...
Page 51: ...50 4 Design and Functions Fig 4 22 Gas with pilot burner and leakage test BT300...
Page 52: ...51 4 Design and Functions Fig 4 23 Gas without pilot burner and leakage test BT300...
Page 53: ...52 4 Design and Functions Fig 4 24 Oil without pilot burner BT335...
Page 54: ...53 4 Design and Functions Fig 4 25 Gas without pilot burner and leakage test BT335...
Page 59: ...58 4 Design and Functions Fig 4 28 Leakage test process diagram...
Page 98: ...97 6 Operating Control and Displays...
Page 99: ...98 6 Operating Control and Displays...
Page 103: ...102 6 Operating Control and Displays...
Page 105: ...104 6 Operating Control and Displays...
Page 106: ...105 6 Operating Control and Displays...
Page 107: ...106 6 Operating Control and Displays...
Page 109: ...108 6 Operating Control and Displays...
Page 126: ...125 6 Operating Control and Displays 6 3 4 2 Curve Table Fig 6 37 Curve table window...
Page 246: ...242 10 EU Declaration of Conformity 10 EU Declaration of Conformity...
Page 247: ...243 10 EU Declaration of Conformity...