![Lake Shore 350 User Manual Download Page 97](http://html.mh-extra.com/html/lake-shore/350/350_user-manual_670644097.webp)
4.5.2 Analog Outputs
83
|
www.lakeshore.com
To set Heater Range, first configure the front panel display to show the desired control
loop information, then use the
Heater Range
key on the front panel. A quick way to
access the setting if the control loop information is not already being displayed is to
press
A
,
B
,
C
, or
D
on the front panel to temporarily display the control loop informa-
tion while the new setting is entered. Refer to section 4.2 for details on configuring
the front panel display.
Menu Navigation:
Heater Range
Q
(Off, On, Range 1, Range 2, Range 3, Range 4, Range 5)
Default: Off
Interface Command:
RANGE
4.5.1.5.9 ALL OFF
The
ALL OFF
key is provided as a means of shutting down all control outputs with one
key. It is equivalent to setting the Heater Range parameter of all outputs to Off.
This function is always active even if the keypad is locked or when it is in remote mode.
4.5.2 Analog Outputs
The analog outputs, 3 and 4, are variable DC voltage sources that have a range from
–10 V to +10 V. The voltage is generated by a 16-bit D/A converter with resolution of
0.3 mV or 0.003% of full scale. This output can be configured to a Closed Loop PID,
Zone, Open Loop, Warm Up Supply, or Monitor Out mode. The Closed Loop PID mode
can be used to control temperature. It can also be set up for bipolar PID control, which
is useful when controlling a thermoelectric device. Refer to section 5.4 for more infor-
mation on setting up thermoelectric devices. The Open Loop mode can be used to set
the output to a specific, constant value. Refer to section 4.5.1.4.3 for details on Open
Loop Mode. The Warm Up Supply mode uses the output to drive the programming
input for an external power supply for the purpose of rapidly warming a system to a
user-specified temperature. The Monitor Out mode uses the output to provide a volt-
age proportional to an input sensor reading to be used by an external device such as a
data logger.
The voltage output is designed to provide up to 1 W into a 100
)
heater. The output is cur-
rent limited to slightly over 100 mA, and therefore, a heater value less than 100
)
can
drive the output into current limit. This condition will not damage the output, but it can
result in discontinuous temperature control.
4.5.2.1 Warm Up Supply
Warm Up Supply mode is designed for controlling an external power supply used for
rapidly increasing the temperature in the controlled system, for example, to bring a
system to room temperature in order to change samples. Refer to section 5.5 for more
information on warm up supply operation. Refer to section 3.6.5 for the procedure to
install an external power supply for warm up supply mode.
4.5.2.2 Monitor Out
Refer to section 5.6 for more information on Monitor Out mode.
4.6 Interface
The Model 350 has three computer interfaces: IEEE-488, USB, and Ethernet. Only one
of these interfaces can be active at one time. Use the Interface menu to configure
which interface is active, and to configure the parameters related to the selected
interface.
Menu Navigation:
Interface
Q
Enabled
Q
(USB, Ethernet, IEEE-488)
Default: USB
Summary of Contents for 350
Page 4: ...Model 350 Temperature Controller ...
Page 6: ......
Page 14: ...Model 350 Temperature Controller ...
Page 28: ...14 cHAPTER 1 Introduction Model 350 Temperature Controller ...
Page 53: ...Examples of PID control 2 13 4 ManualOutput 39 www lakeshore com FIGURE 2 4 ...
Page 58: ...44 cHAPTER 2 Cooling System Design and Temperature Control Model 350 Temperature Controller ...
Page 118: ...104 cHAPTER 5 Advanced Operation Model 350 Temperature Controller ...
Page 178: ...164 cHAPTER 7 Options and Accessories Model 350 Temperature Controller ...
Page 192: ...178 cHAPTER 8 Service Model 350 Temperature Controller ...