Suitability
This automatic neutral-to-ground bonding
system requires AC input sources with bonded neutral. This
will be the case in most situations: in a utility feed, at an
external AC hook-up, or a generator with a bonded neutral. If
not, have an electrician look into bonding the source’s neutral
to ground. See also “AC Input and Output Isolation” on page
28.
DC Components
Batteries
The
$XWR3RZHU
system requires a 12
Y
lead-acid deep-cycle
battery or group of batteries to provide the DC current that
the inverter/charger converts to AC power. The battery may
be a flooded, gel, or AGM type.
See “Battery Information” on page
for information on:
•
Estimating the battery size that will meet your
requirements.
•
Designing battery banks.
•
Restrictions on the size of appliances.
For information on cabling and hooking up batteries, see
“Battery Cabling and Hook-up Configurations” on page
.
For detailed information about specific brands of batteries,
consult individual battery manufacturers.
DC Cabling
Definition
DC cabling includes all of the cables and
connectors between the batteries, the DC disconnect and
overcurrent protection device, and the inverter/charger.
Type
All installations require multi-strand insulated cables.
The DC cables must be copper and must be rated 75°C
minimum.
Size and Length
See Table 3 for required DC cable length,
cable size and required fuse size for the
Auto Power
. Wire
size is usually marked on the cables.
Table 3
Minimum Recommended Battery Cable Sizes for
Copper Conductors Rated 75C
Conduit
Free Air
Model
Typical
Amps
(A)
Cable Length
< 10 ft.
Cable Length
< 5 ft.
$XWR3RZHU
2
250
250 kcmil
2/0 AWG
Summary of Contents for 091-269-12-2000