3
INSTALLATION
36
OPTISONIC 6400
www.krohne.com
08/2011 - 4000972602 - MA OPTISONIC 6400 R02 en
Choose "Heating" or "Cooling" to activate energy measurement. The calculation of heating and
cooling is the same, except for the polarity of the calculated energy flow.
To measure the correct energy direction set via "Temperature input
" which temperature
sensor is at the supply side of the installation
If there are no temperature sensors available for connecting, set the "Temperature input" to
"Manual".
Set the location of the flow sensor (supply or return side of the installation) in order to calculate
the correct specific heat of the liquid. Check whether the shown fluid is correct. The type of fluid
is set in the flow sensor installation wizard. In case the fluid is set to water-glycol mixture in the
flow sensor installation wizard the concentration of glycol in water can be set in the
heating/cooling setup menu.
2.4.2.3
Function
Temperature input
Temperature input
Temperature input
Temperature input
Supply temperature
Return temperature
Sensor location
Fluid
Heating
Manual
Manual
Manual
Manual
80.0
°
C
120.0
°
C
Supply
Water
13-04-2010 14:11:09 13 MB free
2.4.2.3
Function
Temperature input
Temperature input
Temperature input
Temperature input
Sensor location
Fluid
Heating
Terminal A at supply
Terminal A at supply
Terminal A at supply
Terminal A at supply
Supply
Water
13-04-2010 14:11:09 13 MB free