4.3 Electrical installation: 2-wire, loop-powered
4.3.1 Compact version
CAUTION!
Output 1 energizes the device and is used for HART
®
communication. If the device has the
second current output option, use a separate power supply to energize output 2. If the device has
a switch output - relay option, use a separate power supply (connect the power supply to the
switch power supply terminals).
Terminals for electrical installation (one output)
Figure 4-1: Terminals for electrical installation (one output)
1
Current output 1
2
Grounding terminal in the housing (if the electrical cable is shielded)
3
Location of the external grounding terminal (at the bottom of the converter)
CAUTION!
•
Use the applicable electrical cables with the cable glands.
•
Make sure that the current is not more than 4 A or that there is 4 A-rated fuse in the
electrical circuit that energizes the device.
•
Make sure that the polarity of the power supply is correct. If the polarity is incorrect, you will
not cause damage to the device but the device will not operate.