OPERATION
112
OPTIFLEX 8200 C/F/S
www.krohne.com
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en
•
After you enter 1.0.0 Advanced Setup
1.0.0 Advanced Setup
1.0.0 Advanced Setup
1.0.0 Advanced Setup menu, 3 × [
] to go to the menu item 1.4.0 Application
1.4.0 Application
1.4.0 Application
1.4.0 Application
Setup
Setup
Setup
Setup.
•
Push [>>>>] to start the procedure.
•
Push [
] or [
] to change the Application Type
Application Type
Application Type
Application Type parameter. If you have the Dynamic Gas-phase
Compensation option, then set this menu item to "LEVEL WITH GAS PHASE COMPENSATION".
If you have the Interface Capability option, then set this menu item to "LEVEL + INTERFACE
MIXED", "LEVEL + INTERFACE UNMIXED" or "INTERFACE (FULLY SUBMERGED PROBE)".
Push [
^
^
^
^
] to go to the next step.
•
ALTERNATIVE STEP A:
ALTERNATIVE STEP A:
ALTERNATIVE STEP A:
ALTERNATIVE STEP A: If you know the dielectric constant value of the tank contents, then
push [>>>>] (Known) to enter the value. Push [>>>>] to move the cursor to the next digit on the right. If
the cursor is on the last digit, push [>>>>] again to go back to the first digit. Push [
] to decrease
the digit value and [
] to increase the digit value. Push [
^
^
^
^
] to go to the next step.
•
ALTERNATIVE STEP B:
ALTERNATIVE STEP B:
ALTERNATIVE STEP B:
ALTERNATIVE STEP B: If you do not know the dielectric constant value of the tank contents,
then push [
] (Unknown) to give the product family. Push [
] or [
] to change the Product
Product
Product
Product
Family
Family
Family
Family parameter. Push [
^
^
^
^
] to go to the next step.
•
Push [
^
^
^
^
] again and again to go back to the Store
Store
Store
Store screen.
•
Push [
] or [
] to set the screen to "STORE YES" and push [
^
^
^
^
].
i
The device will save the new settings and go back to normal mode.
If the device cannot find the level signal after you do the procedure in menu item 1.4.0
1.4.0
1.4.0
1.4.0
Application Setup
Application Setup
Application Setup
Application Setup, then you can also manually change the threshold to find the signal. Do this
procedure:
•
Look at the level pulse amplitude value on left side of the first screen in menu item 2.5.4 Level
2.5.4 Level
2.5.4 Level
2.5.4 Level
Threshold
Threshold
Threshold
Threshold.
i
Make a note of the amplitude of the correct level signal. Use this value to calculate the new
value for the level threshold. The level threshold value used at this time is shown on right
side of the first screen.
•
Push [
] to change the level threshold value.
•
Increase the amplitude of the level threshold value. Push [>>>>] to move the cursor to the next
digit on the right. If the cursor is on the last digit, push [>>>>] again to go back to the first digit.
Push [
] to decrease the digit value and [
] to increase the digit value.
i
This value must be more than the incorrect signal. We recommend that you set the level
threshold at half the amplitude of the correct signal.
•
Push [
^
^
^
^
] again and again to go back to the Store
Store
Store
Store screen. Save the settings.
i
The threshold increases. The device ignores the interference signal and uses the first
signal that it finds.
Interface threshold
The device uses Direct mode to measure the level and interface level of products. If there are
objects in the tank that can cause signal interference, change the interface threshold to ignore
them. Use the same procedure in How to use thresholds
How to use thresholds
How to use thresholds
How to use thresholds to change the interface threshold, but
go to menu item 2.5.5 Interface Threshold
2.5.5 Interface Threshold
2.5.5 Interface Threshold
2.5.5 Interface Threshold.
For more data about the interface threshold, refer to
Function description on page 79 (menu
item 2.5.5).