7.5 Electrical Data AKD-xzzz06
Electrical Data
Units
AKD-
x00306
AKD-
x00606
AKD-
x01206
AKD-
x02406
Rated supply voltage (L1/L2/L3)
V
3 x 120 V to 240 V ±10%
1 x 120 V to 240 V ±10%
3x240 V
±10%
Rated supply input frequency
Hz
50 Hz to 400 Hz ±5% or DC
Rated input power for S1 operation
kVA
1.2
2.38
3.82
7.6
Rated input current
at 1x120 V
A
5.0
9.9
12
-
at 1x240 V
A
5.0
9.9
12
-
at 3x120 V
A
2.3
4.6
9.2
-
at 3x240 V
A
2.3
4.6
9.2
18.3
Permitted switch on/off frequency, mains
1/h
30
Max. inrush current
A
10
10
10
20
Rated DC bus link voltage
(Bus Turn on Delay 3ph 1 sec)
V
170 to 340
Continuous output current ( ± 3%), single-phase or three-phase
at 120 V
Arms
3
6
12
-
at 240 V
Arms
3
6
12
24
Peak output current (for 5 s, ± 3%)
Arms
9
18
30
48
Continuous output power @ rated input current
at 1x120 V
VA
312.5
625
1250
-
at 1x240 V
VA
625
1250
2500
-
at 3x120 V
VA
312.5
625
1250
-
at 3x240 V
VA
625
1250
2500
5000
Peak output power (for 1 s)
at 1x120 V
kVA
0.937
1.875
3.125
-
at 1x240 V
kVA
1.875
3.750
6.250
-
at 3x120 V
kVA
0.937
1.875
3.125
-
at 3x240 V
kVA
1.875
3.750
6.250
10
Technical data for regen circuit
—
Motor inductance min.
at 120 V
mH
1.3
0.6
0.5
0.3
at 240 V
mH
2.5
1.3
1
0.6
Motor inductance max.
mH
250
125
100
60
Thermal dissipation, output stage disable
W
max. 20
max. 20
max. 20
max. 25
Thermal dissipation at rated current
W
31
57
137
175
Noise emission (low speed/high speed fan)
dB
(A)
N/A
33/39
37/43
41/56
Aux. voltage supply (PELV)
V
24 V (±10%, check voltage drop)
-current B, P, T types without/with motor brake
A
0.5 / 1.7
0.6 / 1.8
0.7 / 1.9
1.0 / 2.5
-current M type without/with motor brake
A
0.8 / 2.0
0.9 / 2.1
1.0 / 2.2
1.3 / 2.8
AKD Installation | 7 Technical description and data
Kollmorgen | kdn.kollmorgen.com | October 2017
37