36
Confi guration
Confi guration
Choices
Default
Output 1 (OUT1)
OT1:
RANGE
0–20 mA, 4–20 mA
4-20 mA
CHANNEL
PH/ORP/TMP
PH
PH
BEGIN 4mA (0 mA)
–2.00...16 PH
00.00 PH
END 20 mA
–2.00...16 PH
14.00 PH
ORP
BEGIN 4mA (0 mA)
–1999...1999 mV
END 20 mA
–1999...1999 mV
TMP
°C
BEGIN 4mA (0 mA)
–20...300 °C
Select °C/°F
END 20 mA
–20...300 °C
for “Sensor“
TMP
°F
BEGIN 4mA (0 mA)
–4...572 °F
END 20 mA
–4...572 °F
FILTERTIME
0...120 SEC
0000 SEC
22mA-FAIL
ON/OFF
OFF
HOLD MODE
LAST/FIX
LAST
FIX
HOLD-FIX
(0) 4...22 mA
021.0 mA
Output 2 (OUT2)
OT2:
RANGE
0–20 mA, 4–20 mA
4-20 mA
CHANNEL
PH/ORP/TMP
TMP
PH
BEGIN 4mA (0 mA)
–2.00...16 PH
00.00 PH
END 20 mA
–2.00...16 PH
14.00 PH
ORP
BEGIN 4mA (0 mA)
–1999...1999 mV
END 20 mA
–1999...1999 mV
TMP
°C
BEGIN 4mA (0 mA)
–20...300 °C
Select °C/°F
END 20 mA
–20...300 °C
for “Sensor“
TMP
°F
BEGIN 4mA (0 mA)
–4...572 °F
END 20 mA
–4...572 °F
FILTERTIME
0...120 SEC
0000 SEC
22mA-FAIL
ON/OFF
OFF
HOLD MODE
LAST/FIX
LAST
FIX
HOLD-FIX
(0) 4...22 mA
021.0 mA