3.1
HEAT MODE
Enable or disable the heating mode
1
0
1
1
/
3.2
t_T4_FRESH_H
The refresh time of climate related curves for heating
mode
0.5
0.5
6
0.5
hours
3.3
T4HMAX
The maximum ambient operating temperature for heating
mode
25
20
35
1
℃
3.4
T4HMIN
The minimum ambient operating temperature for heating
mode
-15
-25
15
1
℃
3.5
dT1SH
The temperature difference for starting the unit (T1)
5
2
10
1
℃
3.8
T1SetH1
The setting temperature 1 of climate related curves for
heating mode
35
25
60
1
℃
3.9
T1SetH2
The setting temperature 2 of climate related curves for
heating mode
28
25
60
1
℃
3.10
T4H1
The ambient temperature 1 of climate related curves for
heating mode
-5
-25
35
1
℃
3.11
T4H2
The ambient temperature 2 of climate related curves for
heating mode
7
-25
35
1
℃
3.12
ZONE1 H-EMISSION
The type of zone1 end for heating mode
:
0=FCU(fan coil
unit)
,
1=RAD.(radiator)
,
2=FLH(floor heating)
1
0
2
1
/
3.13
ZONE2 H-EMISSION
The type of zone2 end for heating mode
:
0=FCU(fan coil
unit)
,
1=RAD.(radiator)
,
2=FLH(floor heating)
2
0
2
1
/
3.14
t_DELAY_PUMP
the time that the compressor has run before starting the
pump.
2
2
20
0.5
MIN
4.1
T4AUTOCMIN
The minimum operating ambient temperature for cooling in
auto mode
25
20
29
1
℃
4.2
T4AUTOHMAX
The maximum operating ambient temperature for heating
in auto mode
17
10
17
1
℃
5.1
WATER FLOW TEMP.
Enable or disable the WATER FLOW TEMP.:0=NON,1=YES
1
0
1
1
/
5.2
ROOM TEMP.
Enable or disable the ROOM TEMP.:0=NON,1=YES
0
0
1
1
/
5.3
DOUBLE ZONE
Enable or disable the ROOM THERMOSTAT DOUBLE
ZONE:0=NON,1=YES
0
0
1
1
/
7.1
dT1_IBH_ON
The temperature difference betw een T1S and T1 for
starting the backup heater.
5
2
10
1
℃
7.2
t_IBH_DELAY
The time that the compressor has run before the first
backup heater turns on
30
15
120
5
MIN
7.3
T4_IBH_ON
The ambient temperature for starting the backup heater
-5
-15
10
1
℃
7.7
IBH_LOCATE
IBH/AHS installation location PIPE LOOP=0; BUFFER TANK=1
0
0
0
0
℃
7.8
P_IBH1
Power input of IBH1
0
0
20
0.5
kW
7.9
P_IBH2
Power input of IBH2
0
0
20
0.5
kW
7.10
P_TBH
Power input of TBH
2
0
20
0.5
kW
7.4
dT1_AHS_ON
The temperature difference betw een T1S and T1B for
turning the additional heating source on
5
2
10
1
℃
7.5
t_AHS_DELAY
The time that the compressor has run before starting the
additional heating source
30
5
120
5
MIN
7.6
T4_AHS_ON
The ambient temperature for starting the additional
heating source
-5
-15
10
1
℃
8.1
T1S_H.A_H
The target outlet w ater temperature for space heating
w hen in holiday aw ay mode
25
20
25
1
℃
8.2
T5S_H.A_DHW
The target outlet w ater temperature for domestic hot
w ater heating w hen in holiday aw ay mode
25
20
25
1
℃
12.1
PREHEATING FOR
FLOOR T1S
The setting temperature of outlet w ater during first
preheating for floor
25
25
35
1
℃
12.3
t_FIRSTFH
The time last for preheating floor
72
48
96
12
HOUR
The style of room thermostat
:
0=NON,1=MODE
SET,2=ONE ZONE,3=DOUBLE ZONE
6.1
ROOM THERMOSTAT
0
0
3
1
/
3.7
t_INTERVAL_HEAT
the start time interval of the compressor in HEAT mode
5
5
5
1
MIN
The temperature difference for starting the unit (Ta)
2
1
10
1
℃
3.6
dTSH
152
Summary of Contents for KHC-06RY1
Page 1: ...INSTRUKCJA INSTALACYJNA INSTALATIONMANUAL POMPA CIEP A MONO MONO TYPE HEAT PUMP PL EN...
Page 2: ......
Page 87: ...87...
Page 88: ......
Page 110: ...Tank booster heater n d e d n d Automatic air purge valve r d r manometer d r 110...
Page 161: ...9 5 10 4 161...
Page 171: ...20 21 Automatic air purge valve Pressure relief valve 171...
Page 174: ...NOTE 174...
Page 175: ...NOTE 175...
Page 176: ...kaisai com...