9.4.1 Check the water circuit
9.4 Water piping
All piping lengths and distances have been taken into consideration.
Requirements
The maximum allowed thermistor cable length is 20m. This is the maximum allowable distance between the domestic
hot water tank and the unit (only for installations with a domestic hot water tank).The thermistor cable supplied with the
domestic hot water tank is 10m in length.In order to optimize efficiency we recommend installing the 3-way valve and
the domestic hot water tank as close as possible to the unit.
If the installation is equipped with a domestic hot water tank (field supply), please refer to the domestic hot water tank
Installation And Owner's Manual. If there is no glycol (anti-freeze) in the system there is a power supply or pump failure,
drain the system (as shown in the figure below).
NOTE
If water is not removed from the system in freezing weather when unit is not used, the frozen water may damage the
water circle parts.
NOTE
The unit is equipped with a water inlet and water outlet for connection to a water circuit. This circuit must be provided by a
licensed technician and must comply with local laws and regulations.
The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion
of the water piping.
Example
:
5
4
4.2
4.1
10
FHL1
FHL2
FHLn
19
20
Indoor
Outdoor
1
15
16
14
12
14
Modbus
16
2
Assembly unit
Code
Assembly unit
Main unit
15
Shut-off valve (Field supply)
User interface(accessory)
Filling valve (Field supply)
Automatic air purge valve
Balance or buffer tank (Field supply)
19
Drainage valve (Field supply)
Collector/distributor (Field supply)
Drainage valve
10
P_o: Outside circulation pump (Field supply)
Expansion vessel(field supply)
12
FHL
1…n
Floor heating loop (Field supply)
Filter (Accessory)
Bypass valve (field supply)
14
16
20
Code
1
2
4
4.1
4.2
5
122
Summary of Contents for KHC-06RY1
Page 1: ...INSTRUKCJA INSTALACYJNA INSTALATIONMANUAL POMPA CIEP A MONO MONO TYPE HEAT PUMP PL EN...
Page 2: ......
Page 87: ...87...
Page 88: ......
Page 110: ...Tank booster heater n d e d n d Automatic air purge valve r d r manometer d r 110...
Page 161: ...9 5 10 4 161...
Page 171: ...20 21 Automatic air purge valve Pressure relief valve 171...
Page 174: ...NOTE 174...
Page 175: ...NOTE 175...
Page 176: ...kaisai com...