Switch off all power including the unit power supply and backup heater and domestic hot water tank power supply (if
applicable) before removing the switch box service panel.
WARNING
Field wiring guidelines
Most field wiring on the unit is to be made on the terminal block inside the switch box. To gain access to the terminal block,
remove the switch box service panel (door 2).
9.7.3 Precautions on wiring of power supply
Fix all cables using cable ties.
A dedicated power circuit is required for the backup heater.
Installations equipped with a domestic hot water tank (field supply) require a dedicated power circuit for the booster heater.
Please refer to the domestic hot water tank Installation & Owner's Manual. Secure the wiring in the order shown below.
Lay out the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover
securely.
Follow the electric wiring diagram for electrical wiring works (the electric wiring diagrams are located on the rear side of door
2.
Install the wires and fix the cover firmly so that the cover may be fit in properly.
9.7.4 Safety device requirment
Use the correct screwdriver to tighten the terminal screws. Small screwdrivers can damage the screw head and prevent
appropriate tightening.
Over-tightening the terminal screws can damage the screws.
Attach a ground fault circuit interrupter and fuse to the power supply line.
In wiring, make certain that prescribed wires are used, carry out complete connections, and fix the wires so that outside force
cannot affect the terminals.
Use a round crimp-style terminal for connection to the power supply terminal board. In case it cannot be used due to
unavoidable reasons, be sure to observe the following instructions.
Do not connect different gauge wires to the same power supply terminal. (Loose connections may cause overheating.)
When connecting wires of the same gauge, connect them according to the figure below.
-
-
1. Select the wire diameters( minimum valve) individually for each unit based on the table 9-1 and table 9-2
,
where the rated
current in table 9-1 means MCA in table 9-2. In case the MCA exceeds 63A, the wire diameters should be selected according
to the national wiring regulation.
2. Maximum allowable voltage range variation between phases is 2%.
3. Select circuit breaker that having a contact separation in all poles not less than 3 mm providing full disconnection
,
where MFA
is used to select the current circuit breakers and residual current operation breakers.
129
Summary of Contents for KHC-06RY1
Page 1: ...INSTRUKCJA INSTALACYJNA INSTALATIONMANUAL POMPA CIEP A MONO MONO TYPE HEAT PUMP PL EN...
Page 2: ......
Page 87: ...87...
Page 88: ......
Page 110: ...Tank booster heater n d e d n d Automatic air purge valve r d r manometer d r 110...
Page 161: ...9 5 10 4 161...
Page 171: ...20 21 Automatic air purge valve Pressure relief valve 171...
Page 174: ...NOTE 174...
Page 175: ...NOTE 175...
Page 176: ...kaisai com...