10.5.18 Setting parameters
Order number
Code
State
Default
Minumum
Maximum
Setting
interval
Unit
1.1
DHW MODE
Enable or disable the DHW mode:0=NON,1=YES
1
0
1
1
/
1.2
DISINFECT
Enable or disable the disinfect mode:0=NON,1=YES
1
0
1
1
/
1.3
DHW PRIORITY
Enable or disable the DHW priority mode:0=NON,1=YES
1
0
1
1
/
1.4
DHW PUMP
Enable or disable the DHW pump mode:0=NON,1=YES
0
0
1
1
/
1.5
DHW PRIORITY TIME SET Enable or disable the DHW priority time set:0=NON,1=YES
0
0
1
1
/
1.6
dT5_ON
The temperature difference for starting the heat pump
10
1
30
1
℃
1.7
dT1S5
The correct valve to adjust the output of the compressor.
10
5
40
1
℃
1.8
T4DHWMAX
The maximum ambient temperature that the heat pump
can operate at for domestic water heating
43
35
43
1
℃
1.9
T4DHWMIN
The minimum ambient temperature that the heat pump can
operate for domestic water heating
-10
-25
5
1
℃
1.10
t_INTERVAL_DHW
the start time interval of the compressor in DHW mode.
5
5
5
1
MIN
1.11
dT5_TBH_ OFF
the temperature difference between T5 and T5S that
turns the booster heater off.
5
0
10
1
℃
1.12
T4_TBH_ON
the highest outdoor temperature the TBH can operate.
5
-5
20
1
℃
1.13
t_TBH_DELAY
the time that the compressor has run before starting the
booster heater
30
0
240
5
MIN
1.14
T5S_DI
the target temperature of water in the domestic hot water
tank in the DISINFECT function.
65
60
70
1
℃
1.15
t_DI_HIGHTEMP.
the time that the highest temperature of water in the
domestic hot water tank in the DISINFECT function will
last
15
5
60
5
MIN
1.16
t_DI_MAX
the maximum time that disinfection will last
210
90
300
5
MIN
1.17
t_DHWHP_RESTRICT
he operation time for the space heating/cooling operation.
30
10
600
5
MIN
1.18
t_DHWHP_MAX
the maximum continuous working period of the heat pump
in DHW PRIORITY mode.
90
10
600
5
MIN
1.20
PUMP RUNNING TIME
the certain time that the DHW pump will keep running for
5
5
120
1
MIN
1.19
DHW PUMP TIME RUN
Enable or disable the DHW pump run as timed and keeps
running for PUMP RUNNING TIME:0=NON,1=YES
1
0
1
1
/
1.21
DHW PUMP DISINFECT
Enable or disable the DHW pump operate when the unit is
in disinfect mode and T5≥ T5S_DI-2:0=NON,1=YES
1
0
1
1
/
2.1
COOL MODE
Enable or disable the cooling mode:0=NON,1=YES
1
0
1
1
/
2.2
t_T4_FRESH_C
The refresh time of climate related curves for cooling
mode
0.5
0.5
6
0.5
hours
2.3
T4CMAX
The highest ambient operation temperature for cooling
mode
52
35
52
1
℃
2.4
T4CMIN
the lowest ambient operating temperature for cooling
mode
10
-5
25
1
℃
2.5
dT1SC
the temperature difference for starting the heat pump(T1)
5
2
10
1
℃
2.6
dTSC
the temperature difference for starting the heat pump(Ta)
2
1
10
1
℃
2.8
T1SetC1
The setting temperature 1 of climate related curves for
cooling mode.
5
10
5
25
1
MIN
2.9
T1SetC2
The setting temperature 2 of climate related curves for
cooling mode.
16
5
25
1
℃
2.10
T4C1
The ambient temperature 1 of climate related curves for
cooling mode.
35
-5
46
1
℃
2.11
T4C2
The ambient temperature 2 of climate related curves for
cooling mode.
25
-5
46
1
℃
2.12
ZONE1 C-EMISSION
The type of zone1 end for cooling mode
:
0=FCU(fan coil
unit)
,
1=RAD.(radiator)
,
2=FLH(floor heating)
0
0
2
1
/
2.13
ZONE2 C-EMISSION
The type of zone2 end for cooling mode
:
0=FCU(fan coil
unit)
,
1=RAD.(radiator)
,
2=FLH(floor heating)
0
0
2
1
/
The parameters related to this chapter are shown in the table below.
2.7
t_INTERVAL_COOL
the start time interval of the compressor in COOL mode
5
5
1
℃
151
Summary of Contents for KHC-06RY1
Page 1: ...INSTRUKCJA INSTALACYJNA INSTALATIONMANUAL POMPA CIEP A MONO MONO TYPE HEAT PUMP PL EN...
Page 2: ......
Page 87: ...87...
Page 88: ......
Page 110: ...Tank booster heater n d e d n d Automatic air purge valve r d r manometer d r 110...
Page 161: ...9 5 10 4 161...
Page 171: ...20 21 Automatic air purge valve Pressure relief valve 171...
Page 174: ...NOTE 174...
Page 175: ...NOTE 175...
Page 176: ...kaisai com...