8.2.2 Mode set control
Cooling or heating mode is set via the room thermostat, water temperature is set on the user interface.
1) When any “CL” of all the thermostats close, system will be set at cooling mode.
2) When any “HL” of all the thermostats close and all “CL” open, system will be set at heating mode.
Space heating
The circulation pumps operation
1) When the system is in cooling mode, which means any “CL” of all the thermostats closes, SV2 keeps
OFF, P_o starts running.
2) When the system is in heating mode, which means one or more “HL” close and all “CL” open, SV2
keeps ON, P_o starts running.
4
4.2
4.1
10
Outdoor
1
FCU1
FCUn
FCU2
FHL1
FHL2
FHLn
19
19
20
5
22
M
Indoor
RT8
RT1
2
17
15
16
14
12
14
16
Code
Assembly unit
Code
Assembly unit
1
Main unit
2
User interface
16
Drainage valve
(Field
4
Balance or buffer tank ( Field supply)
19
Collector/distributor
4.1
Automatic air purge valve
20
Bypass valve
(Field
4.2
Drainage valve
5
P_o: Outside circulation pump
(Field
supply)
RT 1
Low voltage room thermostat
22
SV2: 3-way valve (Field supply
)
RT8
High voltage room
thermostat
10
Expansion vessel (Field
supply)
FHL
1…n
Floor heating loop
(Field
12
Filter (Accessory)
FCU
1...n
Fan coil unit (Field supply
14
Shut-off valve
15
14Shut-off valve
(Field supply)
supply)
supply)
supply)
)
107
Summary of Contents for KHC-06RY1
Page 1: ...INSTRUKCJA INSTALACYJNA INSTALATIONMANUAL POMPA CIEP A MONO MONO TYPE HEAT PUMP PL EN...
Page 2: ......
Page 87: ...87...
Page 88: ......
Page 110: ...Tank booster heater n d e d n d Automatic air purge valve r d r manometer d r 110...
Page 161: ...9 5 10 4 161...
Page 171: ...20 21 Automatic air purge valve Pressure relief valve 171...
Page 174: ...NOTE 174...
Page 175: ...NOTE 175...
Page 176: ...kaisai com...