40
9.7.5 Remove the switch box cover
NOTE
Unit
6kW
8kW
10kW
12kW 3-PH
14kW 3-PH
16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
18
19
19
14
14
14
Wiring size(mm
2
)
4.0
4.0
4.0
2.5
2.5
2.5
MCA : Max. Circuit Amps. (A)
TOCA : Total Over-current Amps. (A)
MFA : Max. Fuse Amps. (A)
MSC : Max. Starting Amps. (A)
RLA : In nominal cooling or heating test condition
,
the input Amps of compressor where MAX. Hz
can operate Rated Load Amps. (A)
KW : Rated Motor Output
FLA : Full Load Amps. (A)
Unit
8kW
10kW
12kW 3-PH
14kW 3-PH
16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
32
32
27
27
27
Wiring size(mm
2
)
8.0
8.0
4.0
4.0
4.0
3-phase 8-16kW standard with backup heater 9kW(3-phase) units RY3
Unit
6kW
8kW
10kW
Maximum
overcurrent
protector(MOP)(A)
31
32
32
Wiring size(mm
2
)
6.0
8.0
8.0
1-phase 6-10kW with backup heater 3kW (1-phase) units RY1
1-phase 6-10kW without backup heater and 3-phase 12-16kW without backup heater
UNIT POWER SUPPLY
1-phase
L
N
L N
LPS
FUSE
UNIT POWER SUPPLY
3-phase
LPS
FUSE
L1
N
L2 L3
L3
N
L2
L1
UNIT POWER SUPPLY
3-phase
LPS
FUSE
L1
N
L2 L3
L3
N
L2
L1
UNIT POWER SUPPLY
1-phase
L N
LPS
FUSE
The ground fault circuit interrupter must be 1 high-speed type of 30mA(<0.1s). Please use 3-core shielded wire.
The default of backup heater is option 3 (for 9kW backup heater). If 3kW or 6kW backup heater is needed, please
ask professional installer to change the Dip switch of S1 to option 1(for 3kW backup heater) or option 2(for 6kW backup
heater), refer to 10.1.1 FUNCTION SETTING.
Stated values are maximum values (see electrical data for exact values).
131
Summary of Contents for KHC-06RY1
Page 1: ...INSTRUKCJA INSTALACYJNA INSTALATIONMANUAL POMPA CIEP A MONO MONO TYPE HEAT PUMP PL EN...
Page 2: ......
Page 87: ...87...
Page 88: ......
Page 110: ...Tank booster heater n d e d n d Automatic air purge valve r d r manometer d r 110...
Page 161: ...9 5 10 4 161...
Page 171: ...20 21 Automatic air purge valve Pressure relief valve 171...
Page 174: ...NOTE 174...
Page 175: ...NOTE 175...
Page 176: ...kaisai com...