3. Press «Enter» to accept the setting.
Input
AII (analog value via frequency converter) is displayed.
4. Press «DOWN» once.
The line for activating the input is displayed.
5. Press the «Right» key.
6. Press «Enter» to switch into setting mode.
The
check box flashes.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.2.4 Network actual pressure
AII 89 psi
AII 1.01 ok ☑ 89 psi
Active line
7. Press «UP».
8. Press «Enter» to accept the setting.
Result The input for the external transducer is now activated.
You have connected an external pressure transducer to a frequency converter (USS proto‐
col).
➤ Assign the input
FC USS to the pressure transducer.
7.14 Commissioning the machine
Checking the controller settings
Section
Complied?
➤ Language correctly set?
➤ Date and time correct?
➤ Display format correctly set?
➤ System pressure setpoint correctly set?
Tab. 71 Checklist of installation conditions
7
Initial Start-up
7.14 Commissioning the machine
138
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
9_9450 03USE
Summary of Contents for ESD 352 SFC
Page 5: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 171: ...KKW SSC 2 03 en 01 BA SIGMA CONTROL FLUID KKW SSC 2 03 01 20130805 113302...
Page 173: ......
Page 175: ...Contents ii Quick user guide Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03 USE...
Page 215: ...Contents iv Service manual Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03USE...
Page 392: ...KKW GBASE 1 00 en ERSATZTEILE 10357405_10 ESD 2C 20130903 115349...