Example: Two machines with different delivery quantities
Local operating mode of the master: Local mode pA/pB Clock.
■ Toggles between system pressure setpoints pA and pB by a clock program.
■ At peak load times, pressure is regulated to system set-point pressure pA.
During periods of low air demand, pressure is regulated to system setpoint pB (e.g., at week‐
ends).
■ The machine with the lesser air delivery is the slave.
In times with lower air demand, the machine with the smaller delivery is used more frequently.
Example: Two machines with equal delivery quantities
■ Local operating mode of the master: Local mode pA/pB Cycle.
(Toggles between system pressure setpoints pA and pB by a clock).
The clock ensures even loading of both machines. The system pressure setpoints are set the
same for both machines.
■ During timer period 1, the master regulates to pA and signals the slave for pB.
During timer period 2, the master regulates to pB and signals the slave to pA.
If two machines SIGMA CONTROL 2 are to work in master-slave mode, their controllers must
have the same software version.
➤ Follow the configuration steps as described in table 63 .
Controller Procedure
Chapter
Both
Establishing the electrical connection
Both
Set system pressure setpoints pA and pB. The pressure for switch‐
ing points pA and pB is measured directly at the compressor. Pres‐
sure losses in the network do not need to be taken into account.
Master
Either set up switching times for the clock program
or set switching times for the clock
Master
Set the type of LOAD control (clock program or clock) in local mode. 7.9.4.2
Slave
Set remote mode: pA/pB SC2
Slave
Activate the «Remote control» key
Both
Set IP addresses for Ethernet
Both
Activate controller as master or slave
Tab. 63 Master-slave configuration procedure
7.9.4.1 Establishing the electrical connection
Prepare the following for the Ethernet connection:
■ Ethernet cable, 100 m maximum, depending on connection.
■ For each machine with SIGMA CONTROL 2 :
─ Ethernet connector set
■ For connecting the machines to a network (LAN):
─ 2 Ethernet connection plugs
➤ Make the electrical connections as shown in the table below.
7
Initial Start-up
7.9
Configuring the machine for master control
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
99
Summary of Contents for ESD 352 SFC
Page 5: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 171: ...KKW SSC 2 03 en 01 BA SIGMA CONTROL FLUID KKW SSC 2 03 01 20130805 113302...
Page 173: ......
Page 175: ...Contents ii Quick user guide Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03 USE...
Page 215: ...Contents iv Service manual Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03USE...
Page 392: ...KKW GBASE 1 00 en ERSATZTEILE 10357405_10 ESD 2C 20130903 115349...