8. Press «Enter» to accept the setting.
ok is displayed.
The output is assigned and activated.
7.11.3.7 Selecting the message type (operational, alarm, warning)
1. Press «DOWN» once until message type is displayed as the active line.
2. Press «Enter» to switch into setting mode.
The display of
Message type flashes.
3. Use «UP» to select the corresponding message type.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
5.7.3.1 External message 1
Menu
External message 1
Message name
DI 1.11 ok ☑
td : 1 s ¦ Logic +
Logic
DOR 1.04 ok ☑
Alarm ☑
Example: Fault message type
4. Press «Enter» to accept the setting.
Result The input signal is available as external message 1 and/or as output.
7.12 Activating remote acknowledgement
When warning or fault messages are routed to a remote control center via an output it makes
sense to have these messages acknowledged by the control center.
Acknowledging the message without correcting the cause, however, can lead to machine damage.
Safety-relevant messages such as "Emergency-Off" cannot be acknowledged with this function.
The following conditions must be fulfilled:
■ The "Remote acknowledgement" function and the «Remote control» key are activated.
■ A controller input has been assigned for the acknowledgement signal.
Overview
■ Enter access level 2.
■ Select the
< Configuration ➙ Acknowledgement > menu.
■ Set the "Remote acknowledgement" function.
■ Activate the «Remote control» key
■ Assigning an input
■ Press the «Remote control» key.
Machine damage can result from acknowledging a fault message without remedying its
cause!
➤ Find the fault and then decide to acknowledge or not.
7
Initial Start-up
7.12 Activating remote acknowledgement
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
133
Summary of Contents for ESD 352 SFC
Page 5: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 171: ...KKW SSC 2 03 en 01 BA SIGMA CONTROL FLUID KKW SSC 2 03 01 20130805 113302...
Page 173: ......
Page 175: ...Contents ii Quick user guide Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03 USE...
Page 215: ...Contents iv Service manual Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03USE...
Page 392: ...KKW GBASE 1 00 en ERSATZTEILE 10357405_10 ESD 2C 20130903 115349...