CONNECTING YOUR EQUIPMENT
Plug the equipment into the output receptacles on the rear panel of the UPS.
Ensure that you do not exceed the maximum output rating of the UPS (refer
to the information label or the Electrical Specifications in this manual). DO
NOT PLUG EXTENSION CORDS, ADAPTER PLUGS OR SURGE STRIPS
INTO THE OUTPUT RECEPTACLES OF THE UPS, there is a risk of damag-
ing the UPS and/or connected equipment.
CAUTION! DO NOT connect a laser printer, copier, vacuum cleaner or
any other large electrical device into the output receptacles of the UPS.
CONNECTING THE UPS TO AN AC SOURCE
CAUTION - To reduce the risk of fire, connect only to a utility powered circuit
with 20 amperes maximum branch circuit over-current protection in accor-
dance with the National Electric Code, ANSI/NFPA 70. Plug the UPS into a
two pole, three wire, grounded receptacle only. The AC wall outlet shall be
near the UPS and easily accessible. The plug on the input power cord on this
UPS series is intended to serve as a disconnect device. DO NOT PLUG THE
UPS INTO EXTENSION CORDS, ADAPTER PLUGS, SURGE STRIPS OR
POWER STRIPS. DO NOT CUT THE INPUT PLUG OFF AND ATTEMPT TO
HARDWIRE THIS UPS, DOING SO WILL VOID THE WARRANTY.
CONNEXION DE L'ONDULEUR À UNE SOURCE C.A.
ATTENTION! Pour réduire les risques d'incendie, faites le raccordement
uniquement sur un circuit d'alimentation électrique équipé d'un dispositif de
protection de surintensité de circuit de dérivation de maximum 20 ampères,
conformément au Code national de l'électricité, ANSI/NFPA 70. Branchez
l'onduleur uniquement sur une prise bipolaire à trois fils mise à la terre. NE
BRANCHEZ PAS L'ONDULEUR SUR UNE RALLONGE, UN ADAPTATEUR,
UN LIMITEUR DE SURTENSION OU UNE BARRE MULTIPRISES. NE
COUPEZ JAMAIS LE CONNECTEUR D'ENTRÉE POUR TENTER DE
CÂBLER CET ONDULEUR; CECI ANNULERA LA GARANTIE.
CHECKING THE SITE WIRING FAULT
After plugging the UPS into the AC wall outlet, check the Site Wiring Fault
(SWF) icon on the front panel of the UPS. If the SWF icon is illuminated, the
UPS is plugged into an improperly wired AC wall outlet. If the UPS indicates a
Site Wiring Fault (SWF), have a Qualified Electrician correct the problem.
CHARGING THE BATTERY
The UPS will charge the internal batteries whenever the UPS is connected to
an AC source and there is an acceptable AC voltage present (90-150VAC). It
is recommended that the UPS's batteries be charged for a minimum of 4
hours before use. The UPS may be used immediately, however, the “On-
Battery” runtime may be less than normally expected. NOTE: If the UPS is
going to be out of service or stored for a prolonged period of time, the batter-
ies must be recharged for at least twenty-four hours every ninety days.