10. Selection of Analog output function
This section describes the definition of analog output voltage between "AM" & "ACOM".
Refer to Section-1.2.2 for the internal circuit structure.
Relative parameter
Pr.37 -- AM_SELECT
Pr.38 -- AM_GAIN
Auxiliary Analog Output Terminal "AM" is provided for analog meter display, or other applications
Requiring the analog output signal.
"AM_SELECT" is used to select desired signal, which will output to AM terminal.
"AM_GAIN" is used to fine tuning the output voltage level.
User may select any of the four signals in the Table for output to the "AM" terminal.
Pr.37
AM Terminal Function Output Ratio
Remarks
0
HZ Signal
+5V*((Pr.57) / (Pr.15))
1
Reserve
2
Vdc Signal
+5V*((Pr.59) / 1000)
3
Vout Signal
+5V*((Pr.60) / (2 * Pr.84))
4~6
Reserve
7
PID Output
+5V*(PID Output)
8
PID
Bias Input from AI1
If DIx(54)=ON, +5V*(PID Boost * (PID Bias Input from AI1))
If DIx(54)=OFF, +5V*(PID Boost * PID Output)
9
PID
Bias Input from AI2
If DIx(54)=ON, +5V*(PID Boost * (PID Bias Input from AI2))
If DIx(54)=OFF, +5V*(PID Boost * PID Output)
10
PID
Bias Input from AI3
If DIx(54)=ON, +5V*(PID Boost * (PID Bias Input from AI3))
If DIx(54)=OFF, +5V*(PID Boost * PID Output)
11
PID
Bias Set by Pr.28
If DIx(54)=ON, +5V*(PID Boost * (PID Bias Set by Pr.28))
If DIx(54)=OFF, +5V*(PID Boost * PID Output)
Refer to
Appendix
A
12
Constant voltage
+5V*((Pr.38)/255)
13~16 Reserve
17
Heat Sink Temperature +5V*((Pr.62)/100)
For PDAN
series only
Recommend interface circuit to external analog meter:
PD inverter
AM
ACOM
Analog Meter
1V/1mA
5k
Gain
(Pr.38)
Desired output
signal select by Pr.37
First use Pr.37 to select desired output signal.
And let Pr.38=250.
Then adjust variable resistor for trimming to correct position.
If necessary, modify Pr.38 for fine-tuning.
Refer to Sec.1.2 for hardware structure.