34
time
time
time
time
JOG
SPD1
SPD2
SPD3
Pr.19
Pr.21
Pr.24
Pr.27
Normal Speed
time
time
RUN
8.6 DIx_Select = 6, OH (Over Heat) function (Also refer to Section 8.30)
When the input terminal is activated, the inverter will disable the output transistors, and show
OH
alarm message on the
display. Refer to mode-30, for complementary function.
8.7 DIx_Select = 7, TMIA
Tim er/C o u n ter
C lo ck In
D I2 (2 8 )
o r D I4 (2 8 )
In tern al T im e B ase
(0 .1 S eco n d )
T M IA (D Ix = 7 )
o r T M IB (D Ix = 11 )
o r T M IC (D Ix = 3 6 )
F u n ctio n al b lo ck d iag ram o f Tim er/C o u n ter m o d u le
T M O A (D O x = 1 4 )
o r T M O B (D O x = 2 0 )
o r T M O C (D O x = 4 2 )
Note: Only when select DI2(28) or DI4(28), the Timer/Counter Module will be configured as Counter Module.
Otherwise, it is configured as Timer Module.
When configured as a Timer, the Internal 0.1 Second time base signal is selected to be the clock input of the
Timer/Counter Module.
If configured as a Counter, the terminal of DI2 & DI4 that was assigned to mode-28 will become the clock input of the
Timer/Counter Module.
When digital input DIx is assigned to
TMIA
function, it serves as
Input of the OFF-DELAY
timer. User must assign a
digital output DOx , which select
TMOA
function to serve as the output of this timer. And the
timer time
will be
defined in Pr.71. (Refer to Sec.8.94)
When the timer input TMIA is ON, the timer output TMOA will be ON immediately.
If the TMIA become OFF, the timer will start counting time. After waiting the specified time period of Pr.71, then the
TMOA become OFF too.
Note:
When use as Counter mode, the maximum clock input rate is
1000Hz. There is only one internal Timer/Counter Block; you can
use only one Timer/Counter, either TYPE A or TYPE B or TYPE
C.
8.8 DIx_Select = 8, ON-BB
When any DIx selecting this function, activate the input DIx will
BLOCK the BASE
signal to all transistors
immediately in order to disable the inverter output. When the input is OFF again, the inverter will execute
Speed Search
process
.
Refer to Sec.11, the special function for
Speed Search process
.
Also Refer to Sec.8.18 for complement function.
8.9 DIx_Select = 9, FJR
When selected DIx is ON, it will force the inverter execute
Forward-Jog-Run
without RUN Command.
8.10 DIx_Select = 10, RJR
When selected DIx is ON, it will force the inverter execute
Reverse-Jog-Run
without RUN Command.
TMIA
TMOA
Pr.71
/TMOA