19
Pr.17 SKIP_FREQUENCY
This parameter can prevent the inverter running at the resonant point of mechanical system.
Pr.18 SKIP_BAND
This parameter defines the skip range.
HZ desire
HZ outpu
t
Pr.18
Pr.18
Pr.15
Pr.18
Pr.17
Pr.19 JOG SPEED
(Refer to Section 8.2~8.5, 8.80~8.83 & 12)
This parameter determines the running frequency when JOG speed is required.
Pr.20 JOG ACC/DEC
(Refer to 8.2~8.5, 8.84)
Defines the acceleration and deceleration rate when JOG command is in execution, or when DIx(84) is ON.
Pr.21 SPD1 SPEED SET
(Refer to Section 8.2~8.5, 8.80~8.83 & 12)
This parameter determines the running frequency when SPD1 speed is required.
Pr.22 SPD1 ACC TIME
(Refer to 8.2~8.5, 8.85)
Defines the acceleration rate when SPD1 command is in execution, or when DIx(85) is ON.
Pr.23 SPD1 DEC TIME
(Refer to 8.2~8.5, 8.85)
Defines the deceleration rate when SPD1 command is in execution, or when DIx(85) is ON.
Pr.24 SPD2 SPEED SET
(Refer to Section 8.2~8.5, 8.80~8.83 & 12)
This parameter determines the running frequency when SPD2 speed is required.
Pr.25 SPD2 ACC TIME
(Refer to 8.2~8.5, 8.86)
Defines the acceleration rate when SPD2 command is in execution, or when DIx(86) is ON.
Pr.26 SPD2 DEC TIME
(Refer to 8.2~8.5, 8.86)
Defines the deceleration rate when SPD2 command is in execution, or when DIx(86) is ON.
Pr.27 SPD3 SPEED SET
(Refer to Section 8.2~8.5, 8.80~8.83 & 12)
This parameter determines the running frequency when SPD3 speed is required.
PDAN series: Refer to Appendix A for PID function.
Pr.28 SPD3 ACC TIME
(Refer to 8.2~8.5, 8.87)
Defines the acceleration rate when SPD3 command is in execution, or when DIx(87) is ON.
PDAN series: Refer to Appendix A for PID function.
Pr.29 SPD3 DEC TIME
(Refer to 8.2~8.5, 8.87)
Defines the deceleration rate when SPD3 command is in execution, or when DIx(87) is ON.
PDAN series: Refer to Appendix A for PID function.
Pr.30 FREE RUN STOP
If Pr.30 = 0, when stop, inverter gradually decreasing its output frequency and ramp down to stop. If Pr.30 = 1, when
stop, inverter disables output immediately, the motor free run.
Pr.31 REVERSE INHIBIT
If Pr.31 = 0, Inverter may run in both direction.
If Pr.31 = 1, Reverse Run is inhibited.
Pr.32 POWER FACTOR & FILTER
This parameter composed of two factors:
Pr.32 = aa.bb,
separated by decimal point
.
aa: Rated Power Factor value from motor nameplate
bb: Filter constant for Sensor-less compensation
Pr.33 DISCHARGE_ENABLE
If Pr.33 = 0, Discharge circuit is Disabled.
If Pr.33 = 1, Discharge circuit is Enabled.
The discharge transistor will ON if the following conditions are met:
a. Inverter is Running, and
b. Inverter has no alarm, and
c. Inverter checks the VDC>117%, and
d. Only when Inverter is Deceleration.
If Pr.33 = 2, Discharge circuit is Enabled.
The discharge transistor will ON if the following conditions are met:
a. Inverter is Running, and
b. Inverter has no alarm, and
c. Inverter checks the VDC>117%
No matter the inverter is deceleration or not.