21
Pr.55 A/D CONVERTER CHANNEL SELECT
(Refer to Section 13.3)
Pr.56 A/D CONVERSION DATA
(Refer to Section 13.3)
Pr.57 HZ
(Refer to Section 13.1)
Monitors the output frequency of the inverter.
Pr.58 RPM
(Refer to Section 13.1)
Monitors the motor rotating speed, calculated by Pr.57 (HZ), Pr.52 (POLE), and Pr.53 (GEAR_RATIO).
RPM = ( 120 * HZ / POLE ) * GEAR_RATIO%
PDA/PDE/PDH series: Expressed in Krpm, the display shows “xx.xx” Krpm.
PDAN series: When RPM >= 10000 rpm, Expressed in Krpm, the display shows “xx.xx” Krpm,
When RPM <= 9999 rpm, Expressed in rpm, the display shows “xxxx” rpm .
Pr.59 VDC
(Refer to Section 13.1)
Monitors the internal DC BUS voltage of the inverter, VDC = 1.414 * Vac (line input)
Pr.60 VOUT
(Refer to Section 13.1)
Monitors the output Vrms of the inverter.
Pr.61 Irms, Idc and others
(Refer to Section 13.1)
Pr.62 HEAT SINK TEMPERATURE
Monitors the temperature of internal heat sink. When the temperature exceeds 80 degree, inverter will stop and show
OH alarm.
Pr.63 Digital Input Terminal Status
(Refer to Section 13.2)
Monitors the DI1~DI4 input terminal status.
Digit 3: DI1 Input Terminal Status
Digit 2: DI2 Input Terminal Status
Digit 1: DI3 Input Terminal Status
Digit 0: DI4 Input Terminal Status
Pr.64 Control Input Terminal status
(Refer to Section 13.2)
Monitors the RUN & REV input terminal status.
Digit 1: RUN (or DI5) Input Terminal Status
Digit 0: REV (or DI6) Input Terminal Status
Pr.65 Digital Output Terminal status
(Refer to Section 13.2)
Monitors the DO1, DO2 & RY(1,2) output terminal status.
Digit 2: DO1 Output Terminal Status
Digit 1: DO2 Output Terminal Status
Digit 0: RELAY Output Status
Pr.66 reserve
Pr.67 Operation Mode Selection
Select RUN mode as Standard V/F, Sensor-Less or Torque mode.
Refer to section4.3.
Pr.68 Sensor-Less Boost
This parameter is used under Sensor-Less mode. It will be set to suitable value during Auto-Tuning. User doesn’t have
to change it.
Refer to section4.4.
Pr.69 SLIP constant F1 / F2
Motor constant R1, R2 and L1, L2 are combined into this constant.
Refer to section4.4.
Pr.70 Analog Input Gain
Refer to Section 7.2.12, 7.2.13, 7.2.21, 7.2.22, 7.2.33, 7.2.35.
Pr.71 TIMER TIME
(Refer to Section 8.7)
PDAN series: Refer to Appendix A for PID function.
Pr.72 AUTO RUN MODE SELECT
(Refer to Section 12)
Pr.73 TIME PERIOD FOR AUTO RUN STEP1&6
(Refer to Section 12)
Pr.74 TIME PERIOD FOR AUTO RUN STEP2&7
(Refer to Section 12)
Pr.75 TIME PERIOD FOR AUTO RUN STEP3&8
(Refer to Section 12)
Pr.76 TIME PERIOD FOR AUTO RUN STEP4&9
(Refer to Section 12)
Pr.77 TIME PERIOD FOR AUTO RUN STEP5&10
(Refer to Section 12)
Pr.78 MOTOR RATING
Refer to the description of Pr.51.
Pr.79 RESTART TYPE SELECT
(Refer to Section 11)
Pr.80 RESTART STALL LEVEL
(refer to section 11)
Pr.81 SPEED SEARCH DEC TIME
(Refer to Section 11)
Pr.82 VOLTAGE RECOVER TIME
(Refer to Section 11)
Pr.83 IGBE GUARD TIME
This parameter defines the guard time for preventing IGBT short between upper and lower arm.
Only factory can
modify this parameter. Consult factory if modification is necessary.