56
Appendix A
:
PID Function
The PID function is for PDAN series only.
A-1 PID Parameter
Pr.73 PID Input Select
This parameter composed by “X” & “Y” separated by decimal point, the X value is used to select the PID Set signal
source for PID block, and the Y value is used to select the PID FB signal source for PID block.
The equivalent source for selection value “X” or “Y” is:
Pr.73
Description
0
Constant value defined by Pr.27 (0.00~100.00%)
1
From Analog Input AI1
,
0 ~ +5V
è
0~0x7FFF
2
From Analog Input AI2
,
0 ~ +5V
è
0~0x7FFF
3
From Analog Input AI3
,
0 ~ +5V
è
0~0x7FFF
4
From Analog Input AI1
,
+5V ~ 0
è
0~0x7FFF
5
From Analog Input AI2
,
+5V ~ 0
è
0~0x7FFF
6
From Analog Input AI3
,
+5V ~ 0
è
0~0x7FFF
10
DI2(28) Clock Input, the value calculate as:
0x7FFF * (Clocks Input from DI2(28) per 13.2ms / Pr.71)
Pr.28 PID PID Bias (0.1~100.0%)
Pr.29 PID Boost (0.0~500.0%)
Pr.74 PID Preset (0.1~100.0%)
Pr.75 PID P Gain
Pr.76 PID I Gain
Pr.77 PID D Gain
Note: when use PID block function, do not use other function of Pr.73~77
A-2 Digital Input Function
DIx
Function
Description
50
PID Enable
If DIx(50) = OFF, PID block disabled.
If DIx(50) = ON, PID block enabled.
51
PID Hold
If DIx(51) = OFF, PID Integrator normal.
If DIx(51) = ON, PID Integrator Hold.
52
PID Clear
If DIx(52) = ON, PID Integrator Clear.
53
PID Preset
If DIx(53) = ON, PID Integrator preset to the value defined by Pr.74
54
PID Bias Enable
If DIx(54) = ON, Bias = Bias Input Enable.
If DIx(54)=OFF, Bias = 0
55
PID Boost Enable If DIx(55) = ON, Boost = Pr.29 (0.0~500.0%)
If DIx(55) = OFF, Boost = 100.0%.
when DIx(55) = ON, PID output will hold on original value, it is
similar to DIx(51)
A-3 Speed Source
Pr.40
Speed Source
40
Set Frequency = PID Output
48
If DIx(54) = ON, Set Frequency = (PID Boost * (PID Bias Input from AI1))
If DIx(54) = OFF, Set Frequency = (PID Boost * PID Output)
49
If DIx(54) = ON, Set Frequency = (PID Boost * (PID Bias Input from AI2))
If DIx(54) = OFF, Set Frequency = (PID Boost * PID Output)
50
If DIx(54) = ON, Set Frequency = (PID Boost * (PID Bias Input from AI3))
If DIx(54) = OFF, Set Frequency = (PID Boost * PID Output))
51
If DIx(54) = ON, Set Frequency = (PID Boost * (PID Bias Set by Pr.28))
If DIx(54) = OFF, Set Frequency = (PID Boost * PID Output
A-4 Analog Function
Pr.37
AM Output
7
PID Output
8
If DIx(54) = ON, AM = +5V * (PID Boost * (PID Bias Input from AI1))
If DIx(54) = OFF, AM = +5V * (PID Boost * PID Output)
9
If DIx(54) = ON, AM = +5V * (PID Boost * (PID Bias Input from AI2))
If DIx(54) = OFF, AM = +5V * (PID Boost * PID Output)
10
If DIx(54) = ON, AM = +5V * (PID Boost * (PID Bias Input from AI3))
If DIx(54) = OFF, AM = +5V * (PID Boost * PID Output)
11
If DIx(54) = ON, AM = +5V * (PID Boost * (PID Bias Set by Pr.28))