22
Pr.84 INPUT SUPPLY LINE_VOLTAGE
This parameter defines the normal working voltage of the inverter.
According to this parameter, the inverter calculates all voltage dependent values.
l
OP Trip Voltage (VDC) = 1.414 * Pr.84 * 130%
l
UP trip Voltage (VDC) = 1.414 * Pr.84 * 70%
l
OP Recover Voltage (VDC) = 1.414 * Pr.84 * 120%
l
UP Recover Voltage (VDC) = 1.414 * Pr.84 * 80%
l
Contactor On Voltage (VDC) = 1.414 * Pr.84 * 69%
l
Contactor Off Voltage (VDC) = 1.414 * Pr.84 * 65%
Note: The "Contactor" means the device used to BY-PASS the Charging Resistor.
It may be a RELAY or a SCR instead.
There is no contactor in PDE-2007/2015
l
Discharge Start Voltage (VDC) = 1.414 * Pr.84 * 117%
Note: there is no internal discharge transistor in PDE-2007/15
Pr.85 INVERTER RATED CURRENT
This parameter defines the rated output current of the inverter.
Pr.86 IRMS ADJUST
This parameter is used to adjust the IRMS data reading.
Pr.87 VDC ADJUST
This parameter is used to adjust the VDC data reading (Refer to Section 13.1).
Pr.88 MAXIMUM OUTPUT VOLTAGE (%)
The parameter determines maximum output voltage when running at maximum frequency. Refer to description of Pr.10,
Pr.11 and Pr.15.
Pr.89 AI1_LOW
This parameter is used to record the A/D converter data when "AI1" input terminal is connected to "ACOM" terminal.
(JP1 5V)
Pr.90 AI1_HIGH
This parameter is used to record the A/D converter data when "AI1" input terminal is connected to "+5V" voltage
source. (JP1 5V)
Pr.91 AI2_LOW
This parameter is used to record the A/D converter data when "AI2" input terminal is connected to "ACOM" terminal.
(JP2 5V)
Note: this parameter also used by AI3
.
Pr.92 AI2_HIGH
This parameter is used to record the A/D converter data when "AI2" input terminal is connected to "+5V" terminal. (JP2
5V)
Note: this parameter also used by AI3
.
Pr.93 UNIT_NUMBER & BAUD_RATE (only for communication option card)
While using serial communication control, this parameter is used to define the BAUD RATE, PROTOCOL and UNIT
NUMBER (or station address).
Refer to section 15
Pr.94 PARAMETER RELOAD
(Refer to Section 5.3)
Pr.95 MEMORY PROTECT
(Refer to Section 5.2)
Pr.96 FACTORY WRITE ENABLE
(Refer to Section 5.2)
Pr.97 VERSION
This parameter indicates the software revision of this inverter.
Pr.98 MONITOR (I) (Refer to Section 13)
Pr.99 MONITOR (HZ) (Refer to Section 13)
By changing Pr.98 and Pr.99, user can select any two variables for frequent monitoring.
Note: For PDE series, Pr.61 (Irms) always shows 0.0 ampere. User can monitor other important variable by changing
this parameter.