Pr.34 UP/OP RESTART_ENABLE
(Refer to Section 11)
If Pr.34 = 1, when power come back normal, the Inverter will restart automatically.
Pr.35 STALL_LEVEL
This parameter defines the current limit level (%) while STALL process.
Pr.36 BASE BLOCK TIME
(Refer to Section 11)
When UP/OP occurs or DIx(8 or 18) is ON, this parameter guarantees the minimum time to disable the inverter output.
Pr.37 AM SELECT
(Refer to Section 10)
Select desired variables to appear at analog output terminal.
Pr.38 AM GAIN
(Refer to Section 10)
Select desired gain ratio for analog output terminal.
Pr.39 CONTROL COMMAND SELECT
(Refer to Section 6)
This parameter determines the type of FWD/REV, RUN/STOP control method.
Pr.40 SPEED INPUT SELECT
(Refer to Section 7)
This parameter defines the source and type for determining the running frequency.
Pr.41 DI1 FUNCTION SELECT
(Refer to Section 8)
Defines the function for input terminal DI1.
Pr.42 DI2 FUNCTION SELECT
(Refer to Section 8)
Defines the function for input terminal DI2.
Pr.43 DI3 FUNCTION SELECT
(Refer to Section 8)
Defines the function for input terminal DI3.
Pr.44 DI4 FUNCTION SELECT
(Refer to Section 8)
Defines the function for input terminal DI4.
Pr.45 DO1 FUNCTION SELECT
(Refer to Section 9)
Defines the function for output terminal DO1.
Pr.46 DO2 FUNCTION SELECT
(Refer to Section 9)
Defines the function for output terminal DO2.
Pr.47 RELAY FUNCTION SELECT
(Refer to Section 9)
Defines the function for output RELAY terminal RY1&RY2.
Pr.48 Irms/Idc DETECTOR THRESHOLD LEVEL
(Refer to Section 9.13)
This parameter is used to define the threshold level for
Current Over Detector
module.
Pr.49 HZ DETECTOR THRESHOLD LEVEL
(Refer to Section 9.2)
Pr.50 HZ DETECTOR TOLERANCE
(Refer to Section 9.2)
Pr.49 and Pr.50 are used for
SPE, SPNE, SPO and SPNO
output functions.
Pr.51 THERMAL TRIP TIME
This parameter defines the OVER LOAD trip time of the
INTERNAL THERMAL RELAY.
If Pr.51=0, the THERMAL RELAY function is disabled.
Pr.78 MOTOR RATING
If the inverter's rating capacity is larger than the motor in use, this
parameter can be adjusted to protect the motor.
This parameter is defined as the percentage level of the inverter
rating.
Pr.52 POLE
(Refer to Section 13.1)
This parameter defines the POLE number of the motor in use.
Pr.53 GEAR_RATIO
(Refer to Section 13.1)
Pole & Gear Ratio parameters will be used for RPM (Pr.58) calculation.
RPM = (120 * HZ / POLE) * GEAR_RATIO%
Pr.54 MONITOR SELECTION
More internal status or value may be monitored.
Pr.54 selects the data shown in Pr.61.
Pr.54=0: Irms (ampere)
Pr.54=1: Irms (% of inverter rating)
Pr.54=2: Irms (% of motor rating)
Pr.54=3: Power Angle
q
(Angle of Current Phase Lag)
Pr.54=4: Output VA=
Irms
Vrms
*
*
3
Pr.54=5: Power Factor PF=
)
cos(
q
Pr.54=6: Watt (ac side) =
)
cos(
*
*
*
3
q
Irms
Vrms
Pr.54=7: Idc (ampere) (For PDA/PDH series only)
Pr.54=8: Idc (% of inverter rating) (For PDA/PDH series only)
Pr.54=9: Watt (dc side) = Vcap*Idc (For PDA/PDH series only)
Pr.54=10: Watt (limit)
Pr.54=11: OL accumulation level
Pr.54=32: Shows timer value when it is used. (For PDAN series only)
TIME
Pr.51
150%
110%