505429-JTG-L-0512
Johnson Controls Unitary Products
75
Electrical Data - Outdoor Unit - AC With Powered Convenience Outlet
Model
Compressors
Outdoor Fan Motor
Pwr Conv Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP
Qty
FLA
(each)
FLA
J07YC
208/230-3-60
1
25.0
39
164
208/230-1-60
1/3
2
2.1
10.0
45.5
60
460-3-60
1
12.2
19
100
460-1-60
1/3
2
1.2
5.0
22.6
30
575-3-60
1
9.0
14
78
575-1-60
1/3
2
0.9
4.0
17.1
25
J10YC
208/230-3-60
2
18.1
28.3
137
208/230-1-60
3/4
2
3.0
10.0
56.8
70
460-3-60
2
9.0
14.0
62
460-1-60
3/4
2
1.6
5.0
28.5
35
575-3-60
2
6.8
10.6
50
575-1-60
3/4
2
1.4
4.0
22.0
25
J10YD
208/230-3-60
2
17.3
27
123
208/230-1-60
3/4
2
3.0
10.0
55.0
70
460-3-60
2
9.6
15
70
460-1-60
3/4
2
1.6
5.0
29.8
35
575-3-60
2
7.7
12
53
575-1-60
3/4
2
1.4
4.0
24.0
30
J12YC
208/230-3-60
2
22.4
35
149
208/230-1-60
3/4
2
3.0
10.0
66.5
80
460-3-60
2
10.6
17
75
460-1-60
3/4
2
1.6
5.0
32.1
40
575-3-60
2
7.7
12
54
575-1-60
3/4
2
1.4
4.0
24.0
30
J12YD
208/230-3-60
2
23.1
36
160
208/230-1-60
3/4
2
3.0
10.0
68.0
90
460-3-60
2
12.2
19
87
460-1-60
3/4
2
1.6
5.0
35.7
45
575-3-60
2
8.7
14
62
575-1-60
3/4
2
1.4
4.0
26.3
30
J15YC
208/230-3-60
2
25.0
39
164
208/230-1-60
1/3
4
2.1
10.0
74.7
90
460-3-60
2
12.2
19
100
460-1-60
1/3
4
1.2
5.0
37.2
45
575-3-60
2
9.0
14
78
575-1-60
1/3
4
0.9
4.0
28.0
35
J15YD
208/230-3-60
2
25.0
39
164
208/230-1-60
1/3
4
2.1
10.0
74.7
90
460-3-60
2
12.2
19
100
460-1-60
1/3
4
1.2
5.0
37.2
45
575-3-60
2
9.0
14
78
575-1-60
1/3
4
0.9
4.0
28.0
35
J20YC
208/230-3-60
2
30.1
47
225
208/230-1-60
3/4
4
3.0
10.0
89.8
110
460-3-60
2
16.7
26
114
460-1-60
3/4
4
1.6
5.0
49.0
60
575-3-60
2
12.2
19
80
575-1-60
3/4
4
1.4
4.0
36.9
45
J20YD
208/230-3-60
2
30.1
47
225
208/230-1-60
3/4
4
3.0
10.0
89.8
110
460-3-60
2
16.7
26
114
460-1-60
3/4
4
1.6
5.0
49.0
60
575-3-60
2
12.2
19
80
575-1-60
3/4
4
1.4
4.0
36.9
45
J25YC
208/230-3-60
2
48.1
75
245
208/230-1-60
3/4
4
3.0
10.0
130.3
175
460-3-60
2
18.6
29
125
460-1-60
3/4
4
1.6
5.0
53.3
70
575-3-60
2
14.7
23
100
575-1-60
3/4
4
1.4
4.0
42.5
50
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
Summary of Contents for Duct R-410A
Page 81: ...505429 JTG L 0512 Johnson Controls Unitary Products 81 Typical J10 12YC Wiring Diagram ...
Page 82: ...505429 JTG L 0512 82 Johnson Controls Unitary Products Typical J10 12YD Wiring Diagram ...
Page 83: ...505429 JTG L 0512 Johnson Controls Unitary Products 83 Typical J15YC Wiring Diagram ...
Page 84: ...505429 JTG L 0512 84 Johnson Controls Unitary Products Typical J20YC Wiring Diagram ...
Page 85: ...505429 JTG L 0512 Johnson Controls Unitary Products 85 Typical J25YC Wiring Diagram ...
Page 86: ...505429 JTG L 0512 86 Johnson Controls Unitary Products Typical J15 20YD Wiring Diagram ...
Page 88: ...505429 JTG L 0512 88 Johnson Controls Unitary Products Typical J10PC Wiring Diagram ...
Page 89: ...505429 JTG L 0512 Johnson Controls Unitary Products 89 Typical J15 20PC Wiring Diagram ...
Page 90: ...505429 JTG L 0512 90 Johnson Controls Unitary Products Typical J15 20PD Wiring Diagram ...
Page 95: ...505429 JTG L 0512 Johnson Controls Unitary Products 95 Typical J25NC Wiring Diagram ...