Altitude/Temperature Correction Factors Figure
The examples below will assist in determining the airflow
performance of the product at altitude.
Example 1:
What are the corrected CFM, static pressure,
and BHP at an elevation of 5,000 ft. if the blower
performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution:
At an elevation of 5,000 ft. the indoor blower will still
deliver 6,000 CFM if the rpm is unchanged. However, the
Altitude/Temperature Correction Factors table must be used to
determine the static pressure and BHP. Since no temperature
data is given, we will assume an air temperature of 70°F. The
table shows the correction factor to be 0.832.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Corrected BHP = 4.0 x 0.832 = 3.328
Example 2:
A system, located at 5,000 feet of elevation, is to
deliver 6,000 CFM at a static pressure of 1.5". Use the unit
blower tables to select the blower speed and the BHP
requirement.
Solution:
As in the example above, no temperature
information is given so 70°F is assumed.
The 1.5" static pressure given is at an elevation of 5,000 ft.
The first step is to convert this static pressure to equivalent
sea level conditions.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
BHP at 5,000 ft. = 3.2 x .832 = 2.66
Altitude/Temperature Correction Factors Table
Air
Temp.
Altitude (Ft.)
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
40
1.060
1.022
0.986
0.950
0.916
0.882
0.849
0.818
0.788
0.758
0.729
50
1.039
1.002
0.966
0.931
0.898
0.864
0.832
0.802
0.772
0.743
0.715
60
1.019
0.982
0.948
0.913
0.880
0.848
0.816
0.787
0.757
0.729
0.701
70
1.000
0.964
0.930
0.896
0.864
0.832
0.801
0.772
0.743
0.715
0.688
80
0.982
0.947
0.913
0.880
0.848
0.817
0.787
0.758
0.730
0.702
0.676
90
0.964
0.929
0.897
0.864
0.833
0.802
0.772
0.744
0.716
0.689
0.663
100
0.946
0.912
0.880
0.848
0.817
0.787
0.758
0.730
0.703
0.676
0.651
0.600
0.650
0.700
0.750
0.800
0.850
0.900
0.950
1.000
1.050
1.100
40
50
60
70
80
90
100
Air Temperature (ºF)
Correction Factor
Sea Level
1000 ft
2000 ft
3000 ft
4000 ft
6000 ft
7000 ft
8000 ft
9000 ft
10000 ft
5000 ft
Summary of Contents for Duct R-410A
Page 81: ...505429 JTG L 0512 Johnson Controls Unitary Products 81 Typical J10 12YC Wiring Diagram ...
Page 82: ...505429 JTG L 0512 82 Johnson Controls Unitary Products Typical J10 12YD Wiring Diagram ...
Page 83: ...505429 JTG L 0512 Johnson Controls Unitary Products 83 Typical J15YC Wiring Diagram ...
Page 84: ...505429 JTG L 0512 84 Johnson Controls Unitary Products Typical J20YC Wiring Diagram ...
Page 85: ...505429 JTG L 0512 Johnson Controls Unitary Products 85 Typical J25YC Wiring Diagram ...
Page 86: ...505429 JTG L 0512 86 Johnson Controls Unitary Products Typical J15 20YD Wiring Diagram ...
Page 88: ...505429 JTG L 0512 88 Johnson Controls Unitary Products Typical J10PC Wiring Diagram ...
Page 89: ...505429 JTG L 0512 Johnson Controls Unitary Products 89 Typical J15 20PC Wiring Diagram ...
Page 90: ...505429 JTG L 0512 90 Johnson Controls Unitary Products Typical J15 20PD Wiring Diagram ...
Page 95: ...505429 JTG L 0512 Johnson Controls Unitary Products 95 Typical J25NC Wiring Diagram ...