505429-JTG-L-0512
Johnson Controls Unitary Products
7
Refrigerant Piping
• Solid core filter-drier(s) ship loose for field installation.
• Liquid and suction line service valves with gauge ports.
• Suction and discharge line service ports accessible
from unit. Ports capped for leak prevention.
• Liquid line magnetic check valves
• Holding charge of R410A refrigerant.
Electrical Requirements
• Single-point connection electrical power.
• Nominal unit electrical characteristics shall be _____ v,
3-ph, 60 Hz. The unit shall be capable of satisfactory
operation within voltage limits of ____ v to _____ v.
• Condenser fan motors and secondary of transformers
shall be grounded.
Unit Controls
• All 24-volt control circuit, powered by a 24 volt
transformer(s) and protected by a resettable breaker.
• Conventional thermostat must provide operation for
both condensing units and heat pumps without an “O”
output from the thermostat.
• Low voltage terminal strip for simple hook-up.
• Compressor motor protection shuts down unit for motor
over-current, over-temperature or low voltage
conditions.
• Safety lockouts provide reset capability at the space
thermostat or base unit should any of the following
standard safety devices trip and shut off compressor:
a. Loss-of-charge/Low-pressure switch.
b. High-pressure switch.
c. Control board diagnostics and fault code display.
d. Safety lockouts send a 24 volt signal to the control
board's "X" terminal, allowing notification to the user
via the thermostat fault light (if present).
e. Control board shall retain last 5 fault codes in non-
volatile memory, which will not be lost in the event of a
power loss. An LED (light-emitting diode) indicator
flashes a fault code that indicates which safety switch
has tripped.
Non-fused Disconnect Switch
• Factory-installed, internally mounted.
• Accessible from outside the unit.
• NEC and UL approved non-fused switch.
• Provides power off lockout capability.
Convenience Outlet
• Factory-installed, internally mounted.
• Accessible from outside the unit.
• 115V, 15 amp GFI receptacle with independent fuse
protection.
• Required voltage provided by factory-installed step-
down transformer or field supplied 115v circuit.
Low-ambient Head Pressure Control
• Standard operation down to 40 °F without a low
ambient kit.
• Operation down to 0°F with a field-installed low ambient
kit accessory. The controller modulates the fan motor
speed in response to liquid line temperature or
pressure.
Coil Guard
Factory or field installed decorative grille shall be placed on
the units to protect condenser coil after installation.
Hail Guard Package
Field installed hail guard package shall protect coils against
damage from hail and other flying debris.
Coated Condenser Coils
Special phenolic or epoxy polymer coating available as a
factory option on both outdoor and indoor coils.
Each Unit Shall Be:
• Covered by a 1-year limited parts warranty on the
complete unit and 5-year on compressor(s).
• In current production with published literature available
to check performance, limitations, specifications, power
requirements, dimensions, operation and appearance.
• Indoor unit shall be equipped with a V-belt drive option
that will permit the blower RPM to be adjusted to meet
the CFM requirements of the air delivery system. (Refer
to Technical Guide for Airflow Capabilities.)
Each Unit Enclosure Shall Have:
• Exterior panels of 18 gauge steel, finished with baked
enamel to provide a long lasting quality appearance
• Removable panels to provide easy access to the
internal components for maintenance and service on
condensing units, heat pumps and air handlers
• Air handling units must have a filter rack that accepts
both 2” and 4” filters.
• The dimensions of each unit shall not exceed those
specified in the manufacture’s literature.
• The minimum application clearances for condensing
units, heat pumps and air handlers must meet those
specified in the manufacturer’s literature.
Summary of Contents for Duct R-410A
Page 81: ...505429 JTG L 0512 Johnson Controls Unitary Products 81 Typical J10 12YC Wiring Diagram ...
Page 82: ...505429 JTG L 0512 82 Johnson Controls Unitary Products Typical J10 12YD Wiring Diagram ...
Page 83: ...505429 JTG L 0512 Johnson Controls Unitary Products 83 Typical J15YC Wiring Diagram ...
Page 84: ...505429 JTG L 0512 84 Johnson Controls Unitary Products Typical J20YC Wiring Diagram ...
Page 85: ...505429 JTG L 0512 Johnson Controls Unitary Products 85 Typical J25YC Wiring Diagram ...
Page 86: ...505429 JTG L 0512 86 Johnson Controls Unitary Products Typical J15 20YD Wiring Diagram ...
Page 88: ...505429 JTG L 0512 88 Johnson Controls Unitary Products Typical J10PC Wiring Diagram ...
Page 89: ...505429 JTG L 0512 Johnson Controls Unitary Products 89 Typical J15 20PC Wiring Diagram ...
Page 90: ...505429 JTG L 0512 90 Johnson Controls Unitary Products Typical J15 20PD Wiring Diagram ...
Page 95: ...505429 JTG L 0512 Johnson Controls Unitary Products 95 Typical J25NC Wiring Diagram ...