505429-JTG-L-0512
Johnson Controls Unitary Products
9
Physical Data
J07 - 25YC and J10 - 20YD Physical Data
Component
Models
J07YC
J10YC
J10YD
J12YC
J12YD
J15YC
J15YD
J20YC
J20YD
J25YC
Nominal Tonnage
7.5
10
10
12.5
12.5
15
15
20
20
25
REFRIGERANT
Refrigerant type
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
Holding charge (lb)
1
(each system)
1
Holding Charge is the amount in the unit as shipped from the factory.
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Operating Charge (lb)
2
2
Includes matched indoor blower unit with 25 ft of piping.
System #1
14.0
18.0
9.9
24.0
11.5
27.0
13.5
33.5
18.8
35
System #2
---
---
9.9
---
11.5
---
13.5
---
18.8
---
DIMENSIONS (inches)
Length
59.1
59.1
59.1
59.1
59.1
59.1
59.1
59.1
59.1
59.1
Width
31.9
31.9
31.9
31.9
31.9
64.1
64.1
64.1
64.1
64.1
Height
44.5
50.0
50.0
50.0
50.0
44.5
44.5
50.0
50.0
50.0
WEIGHTS (lb)
Shipping
390
499
493
499
493
914
899
945
930
945
Operating
387
497
490
497
490
909
894
942
927
942
COMPRESSORS
3
3
All compressors include crankcase heaters.
Type
Single
Scroll
Tandem
Scroll
Single
Scroll
Tandem
Scroll
Single
Scroll
Tandem
Scroll
Single
Scroll
Tandem
Scroll
Single
Scroll
Tandem
Scroll
Quantity
1
1
2
1
2
1
2
1
2
1
Nominal Capacity (Tons)
System #1
7.5
10
5
12.5
6.3
15
7.5
20
10
25
System #2
---
---
5
---
6.3
---
7.5
---
10
---
Capacity Stages
System #1
1
2
1
2
1
2
1
2
1
2
System #2
---
---
1
---
1
---
1
---
1
---
SYSTEM DATA
No. Refrigeration Circuits
1
1
2
1
2
1
2
1
2
1
Suction Line OD (in.)
1 1/8
1 3/8
1 1/8
1 3/8
1 1/8
1 5/8
1 3/8
1 5/8
1 3/8
1 5/8
Liquid Line OD (in.)
5/8
7/8
5/8
7/8
5/8
7/8
5/8
7/8
5/8
7/8
OUTDOOR COIL DATA
Face area (Sq. Ft.)
23.8
29.0
29.0
29.0
29.0
47.5
47.5
58.1
58.1
58.1
Rows
1
1
1
1
1
1
1
1
1
1
Fins per inch
23
23
23
23
23
23
23
23
23
23
Tube diameter (in./MM)
0.71 / 18
0.71 / 18
0.71 / 18
0.71 / 18
0.71 / 18
0.71 / 18
0.71 / 18
0.71 / 18
0.71 / 18
0.71 / 18
Circuitry Type
2-pass
2-pass
2-pass
2-pass
2-pass
2-pass
2-pass
2-pass
2-pass
2-pass
Refrigerant Control
---
---
---
---
---
---
---
---
---
---
CONDENSER FAN DATA
No. Fans / Diameter (in.)
2/24
2/24
2/24
2/24
2/24
4/24
4/24
4/24
4/24
4/24
Type
Axial
Axial
Axial
Axial
Axial
Axial
Axial
Axial
Axial
Axial
Drive type
Direct
Direct
Direct
Direct
Direct
Direct
Direct
Direct
Direct
Direct
No. speeds
1
1
1
1
1
1
1
1
1
1
Number of motors
System #1
2
2
2
2
2
4
2
4
2
4
System #2
---
---
---
---
---
---
2
---
2
---
Motor HP (ea.)
1/3
3/4
3/4
3/4
3/4
1/3
1/3
3/4
3/4
3/4
Rotation
4
4
When viewing the shaft end of the motor.
CW
CW
CW
CW
CW
CW
CW
CW
CW
CW
RPM
850
1100
1100
1100
1100
850
850
1100
1100
1100
Nominal CFM
System #1
7500
9800
9800
9800
9800
15000
7500
19600
9800
19600
System #2
---
---
---
---
---
---
7500
---
9800
---
Summary of Contents for Duct R-410A
Page 81: ...505429 JTG L 0512 Johnson Controls Unitary Products 81 Typical J10 12YC Wiring Diagram ...
Page 82: ...505429 JTG L 0512 82 Johnson Controls Unitary Products Typical J10 12YD Wiring Diagram ...
Page 83: ...505429 JTG L 0512 Johnson Controls Unitary Products 83 Typical J15YC Wiring Diagram ...
Page 84: ...505429 JTG L 0512 84 Johnson Controls Unitary Products Typical J20YC Wiring Diagram ...
Page 85: ...505429 JTG L 0512 Johnson Controls Unitary Products 85 Typical J25YC Wiring Diagram ...
Page 86: ...505429 JTG L 0512 86 Johnson Controls Unitary Products Typical J15 20YD Wiring Diagram ...
Page 88: ...505429 JTG L 0512 88 Johnson Controls Unitary Products Typical J10PC Wiring Diagram ...
Page 89: ...505429 JTG L 0512 Johnson Controls Unitary Products 89 Typical J15 20PC Wiring Diagram ...
Page 90: ...505429 JTG L 0512 90 Johnson Controls Unitary Products Typical J15 20PD Wiring Diagram ...
Page 95: ...505429 JTG L 0512 Johnson Controls Unitary Products 95 Typical J25NC Wiring Diagram ...