J15NC/ND Upflow and Horizontal Airflow Performance
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
J15NC/ND Upflow
(CFM)
Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Std. 3 HP & Field Supplied Drive
Standard 3 HP & Drive
High Static 5 HP & Drive
4500
583
1.1
634
1.3
688
1.5
738
1.9
782
2.3
827
2.6
4750
592
1.2
643
1.4
700
1.8
744
2.1
788
2.4
833
2.7
5000
602
1.2
653
1.4
707
1.9
751
2.2
795
2.6
840
2.9
5250
613
1.3
664
1.5
716
2.1
759
2.4
804
2.7
848
3.1
5500
577
1.1
625
1.4
676
1.6
725
2.3
768
2.6
813
2.9
857
3.2
5750
590
1.2
638
1.4
689
1.7
735
2.5
778
2.8
822
3.1
6000
603
1.3
651
1.6
702
2.3
745
2.7
789
3.0
833
3.3
6250
617
1.5
664
1.7
714
2.6
757
2.9
801
3.2
845
3.5
6500
587
1.4
631
1.6
679
1.8
726
2.8
769
3.1
813
3.4
857
3.8
6750
601
1.6
645
1.8
693
2.0
739
3.0
782
3.4
826
3.7
7000
616
1.8
660
2.0
710
2.9
753
3.3
796
3.6
839
3.9
7250
632
2.1
675
2.3
725
3.2
767
3.6
810
3.9
854
4.2
7500
647
2.3
691
2.5
740
3.5
782
3.9
825
4.2
High Static 5 HP & Field Supplied Drive
J15NC/ND Horizontal
(CFM)
Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Std. 3 HP & Field Supplied Drive
Standard 3 HP & Drive
High Static 5 HP & Drive
4500
585
1.5
634
1.6
687
1.8
735
2.0
780
2.5
827
2.7
875
2.9
4750
595
1.6
644
1.7
697
1.9
741
2.4
787
2.7
834
2.9
5000
605
1.7
655
1.8
708
2.0
749
2.6
795
2.9
842
3.1
5250
617
1.8
666
2.0
719
2.1
757
2.8
804
3.1
851
3.3
5500
582
1.8
629
1.9
678
2.1
731
2.3
767
3.0
813
3.2
860
3.4
5750
594
1.9
642
2.1
691
2.2
737
2.4
778
3.2
824
3.4
871
3.7
6000
608
2.1
655
2.2
705
2.4
744
3.1
789
3.4
835
3.7
6250
622
2.2
670
2.4
719
2.6
756
3.3
801
3.6
847
3.9
6500
589
2.2
637
2.4
684
2.6
733
2.7
769
3.6
814
3.9
860
4.1
6750
604
2.4
652
2.6
699
2.8
738
3.5
782
3.8
827
4.1
873
4.4
7000
620
2.6
667
2.8
715
3.0
752
3.8
796
4.1
841
4.4
7250
636
2.8
683
3.0
731
3.2
766
4.1
811
4.4
856
4.7
7500
652
3.0
700
3.2
738
4.0
781
4.4
825
4.7
High Static 5 HP & Field Supplied Drive
Summary of Contents for Duct R-410A
Page 81: ...505429 JTG L 0512 Johnson Controls Unitary Products 81 Typical J10 12YC Wiring Diagram ...
Page 82: ...505429 JTG L 0512 82 Johnson Controls Unitary Products Typical J10 12YD Wiring Diagram ...
Page 83: ...505429 JTG L 0512 Johnson Controls Unitary Products 83 Typical J15YC Wiring Diagram ...
Page 84: ...505429 JTG L 0512 84 Johnson Controls Unitary Products Typical J20YC Wiring Diagram ...
Page 85: ...505429 JTG L 0512 Johnson Controls Unitary Products 85 Typical J25YC Wiring Diagram ...
Page 86: ...505429 JTG L 0512 86 Johnson Controls Unitary Products Typical J15 20YD Wiring Diagram ...
Page 88: ...505429 JTG L 0512 88 Johnson Controls Unitary Products Typical J10PC Wiring Diagram ...
Page 89: ...505429 JTG L 0512 Johnson Controls Unitary Products 89 Typical J15 20PC Wiring Diagram ...
Page 90: ...505429 JTG L 0512 90 Johnson Controls Unitary Products Typical J15 20PD Wiring Diagram ...
Page 95: ...505429 JTG L 0512 Johnson Controls Unitary Products 95 Typical J25NC Wiring Diagram ...