505429-JTG-L-0512
Johnson Controls Unitary Products
29
115°F
125°F
4500
77
185.3
17.5
92.7
73.7
54.8
-
-
-
175.0
19.1
89.8
70.9
51.9
-
-
-
72
170.5
17.3
119.4
100.5
81.5
62.6
-
-
161.1
18.9
116.2
97.3
78.4
59.4
-
-
67
155.8
17.1
146.1
127.2
108.3
89.3
70.4
-
147.2
18.8
142.6
123.7
104.8
85.8
66.9
-
62
145.5
16.9
145.5
145.5
136.0
117.1
98.2
79.3
137.7
18.6
137.7
137.7
132.2
113.3
94.3
75.4
57
147.3
16.8
147.3
147.3
129.4
110.5
91.6
72.7
140.3
18.5
140.3
140.3
122.6
103.6
84.7
65.8
5250
77
189.1
17.6
107.3
80.6
59.3
-
-
-
178.3
19.2
107.1
77.6
56.2
-
-
-
72
174.1
17.4
130.7
109.5
88.2
66.9
-
-
164.2
19.1
127.5
106.2
84.8
63.5
-
-
67
159.0
17.2
154.2
138.3
117.1
95.8
74.5
-
150.1
18.9
147.9
134.7
113.4
92.1
70.7
-
62
148.5
17.0
148.5
148.5
147.1
125.8
104.5
83.3
140.3
18.7
140.3
140.3
140.3
122.2
100.4
79.1
57
150.4
16.9
150.4
150.4
140.0
118.7
97.4
76.2
143.0
18.6
143.0
143.0
132.7
112.1
90.0
68.7
6000
77
192.9
17.7
121.9
87.4
63.8
-
-
-
181.6
19.3
124.4
84.3
60.5
-
-
-
72
177.6
17.5
142.1
118.5
94.8
71.2
-
-
167.3
19.2
138.8
115.0
91.3
67.6
-
-
67
162.2
17.3
162.2
149.5
125.9
102.3
78.6
-
152.9
19.0
152.9
145.8
122.1
98.3
74.6
-
62
151.5
17.0
151.5
151.5
158.2
134.5
110.9
87.3
142.9
18.8
142.9
142.9
142.9
131.2
106.6
82.8
57
153.4
17.0
153.4
153.4
150.5
126.9
103.3
79.6
145.7
18.7
145.7
145.7
142.8
120.6
95.4
71.6
6750
72
179.0
17.5
151.7
126.0
100.2
74.4
-
-
165.5
18.3
144.4
118.5
92.7
66.8
-
-
67
163.5
17.3
163.5
157.2
133.0
107.2
81.5
-
151.3
18.2
151.3
147.7
124.0
98.1
72.3
-
62
152.7
17.0
152.7
152.7
156.0
130.3
104.5
78.7
141.4
17.9
141.4
141.4
141.4
121.6
95.3
69.4
57
154.7
17.0
154.7
154.7
153.2
127.4
101.7
75.9
144.2
17.9
144.2
144.2
142.8
117.7
91.0
65.2
7500
72
180.4
17.5
161.4
133.5
105.5
77.6
-
-
163.7
17.4
150.1
122.1
94.1
66.0
-
-
67
164.8
17.3
164.8
164.8
140.1
112.2
84.3
-
149.7
17.3
149.7
149.7
125.9
97.9
69.9
-
62
153.9
17.0
153.9
153.9
153.9
126.0
98.1
70.2
140.0
17.1
140.0
140.0
140.0
112.0
83.9
55.9
57
155.9
17.0
155.9
155.9
155.9
128.0
100.1
72.1
142.7
17.0
142.7
142.7
142.7
114.7
86.7
58.7
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J15YC/J15NC
(Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65
Summary of Contents for Duct R-410A
Page 81: ...505429 JTG L 0512 Johnson Controls Unitary Products 81 Typical J10 12YC Wiring Diagram ...
Page 82: ...505429 JTG L 0512 82 Johnson Controls Unitary Products Typical J10 12YD Wiring Diagram ...
Page 83: ...505429 JTG L 0512 Johnson Controls Unitary Products 83 Typical J15YC Wiring Diagram ...
Page 84: ...505429 JTG L 0512 84 Johnson Controls Unitary Products Typical J20YC Wiring Diagram ...
Page 85: ...505429 JTG L 0512 Johnson Controls Unitary Products 85 Typical J25YC Wiring Diagram ...
Page 86: ...505429 JTG L 0512 86 Johnson Controls Unitary Products Typical J15 20YD Wiring Diagram ...
Page 88: ...505429 JTG L 0512 88 Johnson Controls Unitary Products Typical J10PC Wiring Diagram ...
Page 89: ...505429 JTG L 0512 Johnson Controls Unitary Products 89 Typical J15 20PC Wiring Diagram ...
Page 90: ...505429 JTG L 0512 90 Johnson Controls Unitary Products Typical J15 20PD Wiring Diagram ...
Page 95: ...505429 JTG L 0512 Johnson Controls Unitary Products 95 Typical J25NC Wiring Diagram ...