505429-JTG-L-0512
Johnson Controls Unitary Products
103
Corner Weights & Center of Gravity J07 Thru 20NC/ND Units
Model
Drive Options
Weight (lbs.)
Center of Gravity
(in.)
4 Point Load Location (lbs.)
6 Point Load Location (lbs.)
Shipping Operating
X
Y
A
B
C
D
A
B
C
D
E
F
Vertical Airflow
J07NC
Std. Mtr. and Drv.
524
498
16.2
26.7
109
128
141
120
71
79
88
97
86
78
High Static Mtr. and Drv.
526
500
16.2
26.7
110
129
142
120
71
79
88
97
87
78
J10NC
Std. Mtr. and Drv.
562
539
15.5
26.8
125
134
146
136
82
86
90
98
94
89
High Static Mtr. and Drv.
573
550
15.5
26.7
127
136
148
139
84
87
91
100
96
91
J10ND
Std. Mtr. and Drv.
564
541
15.5
26.9
126
135
145
136
83
87
91
98
94
89
High Static Mtr. and Drv.
575
552
15.5
26.9
128
137
148
138
84
88
92
100
95
91
J15NC
Std. Mtr. and Drv.
769
737
18.0
34.4
155
185
216
181
101 113 127 148 131 117
High Static Mtr. and Drv.
797
765
18.0
34.4
161
192
224
188
104 117 132 154 136 122
J15ND
Std. Mtr. and Drv.
769
737
18.0
34.4
155
185
216
181
101 113 127 148 131 117
High Static Mtr. and Drv.
797
765
18.0
34.4
161
192
224
188
104 117 132 154 136 122
J20NC
Std. Mtr. and Drv.
908
873
15.8
42.6
179
198
260
235
118 125 134 176 165 154
High Static Mtr. and Drv.
938
903
15.7
42.4
185
204
269
245
122 129 138 182 171 161
J20ND
Std. Mtr. and Drv.
908
873
15.8
42.6
179
198
260
235
118 125 134 176 165 154
High Static Mtr. and Drv.
938
903
15.7
42.4
185
204
269
245
122 129 138 182 171 161
Horizontal Airflow
J07NC
Std. Mtr. and Drv.
524
498
30.1
26.7
118
119
131
130
79
79
79
87
87
87
High Static Mtr. and Drv.
526
500
30.1
26.7
119
120
132
130
79
79
80
88
87
87
J10NC
Std. Mtr. and Drv.
562
539
29.9
26.8
129
129
140
141
86
86
86
94
94
94
High Static Mtr. and Drv.
573
550
30.2
26.7
130
132
145
142
87
87
88
97
96
95
J10ND
Std. Mtr. and Drv.
564
541
29.9
26.9
131
130
140
141
87
87
86
93
94
94
High Static Mtr. and Drv.
575
552
30.2
26.9
132
133
144
142
88
88
89
96
96
95
J15NC
Std. Mtr. and Drv.
769
737
33.2
34.4
169
171
199
197
113 114 114 133 132 131
High Static Mtr. and Drv.
797
765
33.8
34.4
172
181
211
201
114 118 122 142 137 133
J15ND
Std. Mtr. and Drv.
769
737
33.2
34.4
169
171
199
197
113 114 114 133 132 131
High Static Mtr. and Drv.
797
765
33.8
34.4
172
181
211
201
114 118 122 142 137 133
J20NC
Std. Mtr. and Drv.
908
873
30.1
42.6
188
189
249
247
125 126 126 166 165 164
High Static Mtr. and Drv.
938
903
30.6
42.4
191
198
262
252
126 130 133 176 171 167
J20ND
Std. Mtr. and Drv.
908
873
30.1
42.6
188
189
249
247
125 126 126 166 165 164
High Static Mtr. and Drv.
938
903
30.6
42.4
191
198
262
252
126 130 133 176 171 167
CG
LENGTH
WIDTH
A
D
FRONT
REAR
LEFT
RIGHT
DIM X
DIM Y
B
C
A
B
C
D
E
F
VERTICAL POSITION
CG
DIM X
DIM Y
LENGTH
WIDTH
A
D
FRONT
REAR
LEFT
RIGHT
B
C
A
B
C
D
E
F
HORIZONTAL POSITION
Summary of Contents for Duct R-410A
Page 81: ...505429 JTG L 0512 Johnson Controls Unitary Products 81 Typical J10 12YC Wiring Diagram ...
Page 82: ...505429 JTG L 0512 82 Johnson Controls Unitary Products Typical J10 12YD Wiring Diagram ...
Page 83: ...505429 JTG L 0512 Johnson Controls Unitary Products 83 Typical J15YC Wiring Diagram ...
Page 84: ...505429 JTG L 0512 84 Johnson Controls Unitary Products Typical J20YC Wiring Diagram ...
Page 85: ...505429 JTG L 0512 Johnson Controls Unitary Products 85 Typical J25YC Wiring Diagram ...
Page 86: ...505429 JTG L 0512 86 Johnson Controls Unitary Products Typical J15 20YD Wiring Diagram ...
Page 88: ...505429 JTG L 0512 88 Johnson Controls Unitary Products Typical J10PC Wiring Diagram ...
Page 89: ...505429 JTG L 0512 Johnson Controls Unitary Products 89 Typical J15 20PC Wiring Diagram ...
Page 90: ...505429 JTG L 0512 90 Johnson Controls Unitary Products Typical J15 20PD Wiring Diagram ...
Page 95: ...505429 JTG L 0512 Johnson Controls Unitary Products 95 Typical J25NC Wiring Diagram ...