505429-JTG-L-0512
72
Johnson Controls Unitary Products
Drive Selection
1.
Determine Upflow or Horizontal supply duct Application.
2.
Determine desired airflow.
3.
Calculate or measure the amount of external static pressure.
4.
Using the operating point, determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower
performance table. (Linear interpolation may be necessary.)
5.
Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table.
6.
Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.
7.
Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
8.
Determine turns open to obtain the desired operation point.
Example
1.
3250 CFM
2.
1.4 iwg
3.
Using the supply air blower performance table below, the following data point was located: 1100 RPM & 1.8 BHP.
4.
Using the RPM selection table below, Model X is found.
5.
1.8 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.
6.
1100 RPM is within the range of the 2 HP drives.
7.
Using the 2 HP motor and drive, 1 turn open will achieve 1128 RPM.
Airflow Performance
Example Supply Air Blower Performance
(CFM)
Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP RPM BHP RPM BHP
Standard 1.5 HP & Drive
High Static 2 HP & Drive
3000
696
0.9
757
1.1
822
1.2
891
1.3
961
1.3
1019
1.5
1077
1.6
1135
1.8
3250
729
1.1
790
1.3
855
1.4
924
1.5
984
1.6
1042
1.7
1100
1.8
1159
2.0
3500
766
1.3
826
1.5
892
1.6
953
1.6
1010
1.8
1069
1.9
1127
2.0
RPM Selection
Unit Model
HP
Max
BHP
Motor
Sheave
Blower
Sheave
6 Turns
Open
5 Turns
Open
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turn
Open
Fully
Closed
X
Std.
1.5
1.73
1VL40
AK69
N/A
690
743
796
849
902
955
HS
2
2.30
1VL40
AK56
N/A
863
929
995
1062
1128
1194
Summary of Contents for Duct R-410A
Page 81: ...505429 JTG L 0512 Johnson Controls Unitary Products 81 Typical J10 12YC Wiring Diagram ...
Page 82: ...505429 JTG L 0512 82 Johnson Controls Unitary Products Typical J10 12YD Wiring Diagram ...
Page 83: ...505429 JTG L 0512 Johnson Controls Unitary Products 83 Typical J15YC Wiring Diagram ...
Page 84: ...505429 JTG L 0512 84 Johnson Controls Unitary Products Typical J20YC Wiring Diagram ...
Page 85: ...505429 JTG L 0512 Johnson Controls Unitary Products 85 Typical J25YC Wiring Diagram ...
Page 86: ...505429 JTG L 0512 86 Johnson Controls Unitary Products Typical J15 20YD Wiring Diagram ...
Page 88: ...505429 JTG L 0512 88 Johnson Controls Unitary Products Typical J10PC Wiring Diagram ...
Page 89: ...505429 JTG L 0512 Johnson Controls Unitary Products 89 Typical J15 20PC Wiring Diagram ...
Page 90: ...505429 JTG L 0512 90 Johnson Controls Unitary Products Typical J15 20PD Wiring Diagram ...
Page 95: ...505429 JTG L 0512 Johnson Controls Unitary Products 95 Typical J25NC Wiring Diagram ...