505429-JTG-L-0512
Johnson Controls Unitary Products
39
115°F
125°F
4500
77
200.6
18.3
104.5
85.3
66.0
-
-
-
195.5
20.2
102.5
83.2
64.0
-
-
-
72
186.0
17.8
129.7
110.5
91.2
72.0
-
-
181.6
19.6
127.9
108.6
89.4
70.1
-
-
67
171.4
17.4
154.9
135.7
116.4
97.2
77.9
-
167.7
19.1
153.2
134.0
114.7
95.5
76.3
-
62
153.0
16.9
153.0
153.0
136.1
116.8
97.6
78.3
148.7
18.5
148.7
148.7
133.0
113.8
94.5
75.3
57
156.4
16.9
156.4
156.4
139.2
120.0
100.7
81.5
153.5
18.5
153.5
153.5
136.4
117.1
97.9
78.7
5250
77
207.4
18.4
117.0
93.6
71.5
-
-
-
202.4
20.4
115.6
91.6
69.5
-
-
-
72
192.3
18.0
143.0
120.9
98.9
76.8
-
-
188.1
19.8
141.2
119.1
97.0
75.0
-
-
67
177.2
17.5
169.0
148.3
126.2
104.1
82.0
-
173.7
19.2
166.7
146.6
124.6
102.5
80.4
-
62
158.2
17.0
158.2
158.2
147.5
125.4
103.3
81.2
154.0
18.7
154.0
154.0
144.4
122.5
100.2
78.2
57
161.8
17.0
161.8
161.8
150.9
128.8
106.7
84.6
158.9
18.7
158.9
158.9
148.1
126.3
103.9
81.9
6000
77
214.3
18.6
129.6
102.0
77.1
-
-
-
209.4
20.5
128.8
99.9
75.0
-
-
-
72
198.7
18.1
156.3
131.4
106.5
81.6
-
-
194.5
20.0
154.5
129.6
104.7
79.8
-
-
67
183.1
17.6
183.1
160.9
135.9
111.0
86.1
-
179.7
19.4
179.7
159.3
134.4
109.5
84.6
-
62
163.5
17.1
163.5
163.5
158.8
133.9
109.0
84.1
159.3
18.8
159.3
159.3
155.8
131.2
106.0
81.1
57
167.1
17.1
167.1
167.1
162.6
137.6
112.7
87.8
164.4
18.8
164.4
164.4
159.8
135.5
110.0
85.1
6750
72
200.5
18.1
166.3
139.0
111.8
84.5
-
-
196.0
19.9
164.4
137.1
109.8
82.6
-
-
67
184.7
17.6
184.7
169.9
142.6
115.4
88.1
-
181.0
19.4
181.0
168.3
141.0
113.8
86.5
-
62
164.9
17.1
164.9
164.9
162.6
135.4
108.1
80.8
160.4
18.8
160.4
160.4
158.7
131.6
104.2
76.9
57
168.6
17.1
168.6
168.6
166.3
139.1
111.8
84.6
165.6
18.8
165.6
165.6
163.3
136.4
108.8
81.5
7500
72
202.3
18.1
176.2
146.6
117.0
87.4
-
-
197.4
19.9
174.2
144.6
115.0
85.4
-
-
67
186.4
17.6
186.4
178.9
149.3
119.7
90.1
-
182.3
19.3
182.3
177.2
147.6
118.0
88.4
-
62
166.4
17.1
166.4
166.4
166.4
136.8
107.2
77.6
161.6
18.7
161.6
161.6
161.6
132.0
102.4
72.8
57
170.1
17.1
170.1
170.1
170.1
140.5
110.9
81.3
166.8
18.7
166.8
166.8
166.8
137.2
107.6
78.0
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J15YD/J20ND
(Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
1
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
1
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65
Summary of Contents for Duct R-410A
Page 81: ...505429 JTG L 0512 Johnson Controls Unitary Products 81 Typical J10 12YC Wiring Diagram ...
Page 82: ...505429 JTG L 0512 82 Johnson Controls Unitary Products Typical J10 12YD Wiring Diagram ...
Page 83: ...505429 JTG L 0512 Johnson Controls Unitary Products 83 Typical J15YC Wiring Diagram ...
Page 84: ...505429 JTG L 0512 84 Johnson Controls Unitary Products Typical J20YC Wiring Diagram ...
Page 85: ...505429 JTG L 0512 Johnson Controls Unitary Products 85 Typical J25YC Wiring Diagram ...
Page 86: ...505429 JTG L 0512 86 Johnson Controls Unitary Products Typical J15 20YD Wiring Diagram ...
Page 88: ...505429 JTG L 0512 88 Johnson Controls Unitary Products Typical J10PC Wiring Diagram ...
Page 89: ...505429 JTG L 0512 Johnson Controls Unitary Products 89 Typical J15 20PC Wiring Diagram ...
Page 90: ...505429 JTG L 0512 90 Johnson Controls Unitary Products Typical J15 20PD Wiring Diagram ...
Page 95: ...505429 JTG L 0512 Johnson Controls Unitary Products 95 Typical J25NC Wiring Diagram ...