1 Safety Instructions
JetWeb
20
Jetter AG
1.3.2
Hazards after POWER has been turned
OFF
Danger
DANGER resulting from electric shock!
Up to 7 minutes after switching off the operating voltages, capacitors still carry
hazardous residual voltages.
As a precaution, measure the voltage in the DC link circuit (amplifier
terminal) and wait until it has fallen below DC 40 V.
Always
wait at least 7 minutes after switching off the device, before
separating it from the mains or loosening the connections.
Always
wait at least 10 minutes after switching off the device before taking
the following actions:
– Touching the screws of the terminals X1, X62 and X63;
– Disconnecting the terminals and touching the contacts.