6. DISPLAY MESSAGES
6.1 Serious errors
Errors associated with the security of the installation or equipment malfunction. These errors must be
resolved always.
Error
Description
Solution
INT. ERROR
Internal error
Go to the technical service
HA ERROR
Hall A error
Verify the hall A input connections
PROG TIME MAX
Programming time maximum
Program a maneuver below the
maximum allowed time
S.EDGE.CL ERROR
Closing safety edge error
Verify the security edge band
connections when closing
S.EDGE.OP ERROR
Opening safety edge error
Verify the security edge band
connections when opening
TEMP ON
Motor temperature sensor
activated
Verify the motor state and the
temperature sensor connection
TEST.CL ERROR
Closing auto test error
Verify that the security device connected
to the security connection when closing
is in good conditions and correctly
installed
TEST.OP ERROR
Opening auto test error
Verify that the security device connected
to the security connection when opening
is in good conditions and correctly
installed
RSENS NC WHEN
PROG
Control panel programmed without
RSENS connected
Connect the RSEC card and program the
control panel again
RSENS NOT FOUND
Control panel programmed with
RSENS connected and now it is
not connected
Program the control panel again without
RSEC or connect the RSEC again that
was programmed to the control panel
previously
RSENS PROG ERROR
RSENS programming error, are R
and T paired?
Program the transmitter RSENS to the
RSEC receiver card
STOP
Control panel stopped by an STOP Verify that the STOP input has been
activated
INTERNAL ERROR
Internal control panel error
Go to the technical service
DOOR LOCKED RSENS Closed door latch
Open the door's latch before the opening
manoeuvre
RBAND NOT FOUND
Control panel programmed with
RBAND connected and now it is
not connected
Program the control panel again without
using RBAND or connect the RBAND
that was connected to the control panel
previously
RBAND NC WHEN
PROG
Control panel not programmed
with RBAND connected
Connect the RBAND card and program
the control panel again
FC NOT LEARNT
End of course learning error
Verify the intern motor limit switches
ERROR SYNC RSENS
Synchronization error between the
receiver and the transmitter
Program the transmitter RSENS to the
RSEC receiver card
Summary of Contents for GAMMA VERSUS Series
Page 7: ...GAMMA VERSUS MANUAL 7 COD 1257066 Gamma VERSUS Manual v1 13 2 5 Rolling door 2 6 Fast door ...
Page 75: ...GAMMA VERSUS MANUAL 75 COD 1257066 Gamma VERSUS Manual v1 13 ...
Page 78: ...GAMMA VERSUS MANUAL 78 COD 1257066 Gamma VERSUS Manual v1 13 ...
Page 79: ...GAMMA VERSUS MANUAL 79 COD 1257066 Gamma VERSUS Manual v1 13 ...