GAMMA VERSUS MANUAL
45
COD. 1257066 Gamma VERSUS Manual v1.13
Configuration
To enable the electro lock function it is needed to assign the “Electro lock “output value
to a control panel output.
P78
to
P7C
configuration parameters allow assigning an
output value to every available control panel outputs by means of a VERSUS-PROG
programming tool.
PA1
to
PB0
configuration parameters allow assigning an output
value to expanded outputs that are available if TL-CARD-V is connected to the control
panel. Electro lock function is enabled if one or more outputs are configured as “Electro
lock” outputs. If electro lock function has to be disabled, “Electro lock” outputs must
change its value.
Electro lock timer is configured by means of the
P4A
parameter. This parameter can
take values from 0 seconds to several seconds. The units used for this parameter are
seconds.
In control panels models that allow regulation of speed and slow speed, there is the
possibility
of activating the
closing
at maximum speed
function
by setting
P27
configuration parameter
. The closing at maximum speed makes a closing operation of
2 seconds after the slow speed part has finished, ensuring proper
closure
of the
door and that the electrolock closes properly.
Finally, the reverse strike at open function is a function normally associated to the
electrolock function. To enable this function, use the PBD configuration parameter.
There is also possible to control this function by means of assigning this function to one
of the selector switches (P54 to
P5C
parameters).
Operating
After electro lock function is enabled, the control panel executes the electro lock
sequence every time an opening maneuver is started. The electro lock time is divided
in two parts: the first half time before the opening maneuver and the second half time
once the opening maneuver has started.
The reverse strike at open function is done from the position of door CLOSED. If this
function is activated once the open command has been received, the door will close
during a little period of time to be able to liberate the door and then it will begin the
opening sequence. If at the same time, the electrolock function is activated, this will be
kept active during the liberation time of the door.
Notes
Electro lock can be controlled by means of a free voltage output or a voltage output.
In case of the TL-CARD-V all its four outputs are free voltage but in case of the control
panel outputs it depends on the control panel model. Some control panels have 12Vdc
outputs and other control panel models have 12/24Vdc configurable outputs.
If voltage outputs are used electro lock power consumption has to be carefully taken
into account. Control panel output maximum current depends on the control panel
(P4A
Electro
lock
time)/2
Electro
active
+
door
stopped
(P4A
Electro
lock
time)/2
Electro
active
+
door
opening
Summary of Contents for GAMMA VERSUS Series
Page 7: ...GAMMA VERSUS MANUAL 7 COD 1257066 Gamma VERSUS Manual v1 13 2 5 Rolling door 2 6 Fast door ...
Page 75: ...GAMMA VERSUS MANUAL 75 COD 1257066 Gamma VERSUS Manual v1 13 ...
Page 78: ...GAMMA VERSUS MANUAL 78 COD 1257066 Gamma VERSUS Manual v1 13 ...
Page 79: ...GAMMA VERSUS MANUAL 79 COD 1257066 Gamma VERSUS Manual v1 13 ...